Hearth and Home Technologies BEK Installation Instructions Manual Download Page 10

Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05

10

F. Vertical Penetration Framing

Note: 

The fi restop spacer is not required if attic insulation 

shield is used.

Install Attic Insulation Shield

•  Frame opening for attic insulation shield.
•  Attic insulation shield may be installed above or below 

ceiling (see Figure 2.18).

•  Secure with three fasteners on each side.
•  Fold tabs at top of attic shield in toward vent pipe. Tabs 

must keep vent pipe centered within shield.

•  Field construct additional shield height if insulation is 

deeper than height of attic shield.

Attic Above

10 in. (254 mm)

Hole should measure

10 in. x 10 in.

(254 mm x 254 mm)

inside to inside

10 in.

(254 mm)

Figure 2.17  Installing Firestop Spacer

3 fasteners

per side

Attic insulation shield

installed below ceiling.

Attic insulation shield

installed above ceiling.

Bend tabs in
around pipe

Figure 2.18  Installing the Attic Insulation Shield

Fire Risk

Keep loose materials or blown insulation 
from touching the vent pipe.
• 

National building codes recommend using 
attic shield to keep loose materials/blown 
insulation from contacting vent.

•  Hearth & Home Technologies requires 

the use of an attic shield.

WARNING

Install the Firestop Spacer

•  Frame an opening 10 in. by 10 in. whenever the vent 

system penetrates a ceiling/fl oor (see Figure 2.17).

•  Frame the area with the same sized lumber as used in 

ceiling/fl oor joist.

•  When installing a top vent vertical appliance the hole 

should be directly above the appliance, unless the fl ue is 
offset.

•  Do not pack insulation around the vent. Insulation must 

be kept away from the pipe.

Summary of Contents for BEK

Page 1: ...e assembly instructions See the appliance installation instructions for con guration of vent assembly and clearances to pipe If DVP AD adapters are used off the top of the appliance the termination he...

Page 2: ...0ST 90 elbow DVP WS wall shield with heat shield DVP TRAP1 termination cap with telescoping ue and one fastener pack DVP TRAPK2 Vent kit containing DVP90ST 90 elbow DVP WS wall shield with heat shield...

Page 3: ...in 6 in Slip Section Vent Pipe to be used with another piece of pipe DVP12A 3 in 12 in Slip Section Vent Pipe to be used with another piece of pipe DVP12MI 12 in Vent Pipe non unitized can be cut to l...

Page 4: ...0 7 8 in 6 3 4 in to 10 3 4 in GNTC50 5 in to 6 3 4 in 4 7 8 in to 6 5 8 in 7 3 8 in to 11 3 8 in 7 3 8 in to 11 3 8 in Designer 4 in to 5 3 4 in 5 3 4 in to 7 1 2 in 6 3 8 in to 10 3 8 in 8 1 8 in to...

Page 5: ...urations 2 Installing Vent Pipe B Penetrating a Wall Wherever a combustible wall is penetrated the hole must be framed with an interior wall shield DVP WS as shown in Figures 2 3 2 4 This shield maint...

Page 6: ...he pipe section into the appliance collar until all the lances see Fig ure 2 5 have snapped in place Tug slightly on the section to con rm it has completely locked into place Assemble Pipe Sections In...

Page 7: ...an then be attached by tting another pipe section to it and snapping it together as normal Assemble Slip Sections The outer ue of the slip section should slide over the outer ue of the pipe section an...

Page 8: ...e either section see Figure 2 14 so that the seams on both pipe sections are aligned see Figure 2 15 They can then be carefully pulled apart Figure 2 12 Securing Vertical Pipe Sections Figure 2 13 Sec...

Page 9: ...e cap in the same manner See Figure 2 16 If the wall thickness does not allow the required 1 1 2 in heat shield overlap an extended heat shield must be used The extended heat shield will need to be cu...

Page 10: ...17 Installing Firestop Spacer 3 fasteners per side Attic insulation shield installed below ceiling Attic insulation shield installed above ceiling Bend tabs in around pipe Figure 2 18 Installing the A...

Page 11: ...rom roof to lowest discharge opening 24 in min 610 mm Roof Pitch H Min Ft Roof Pitch H Min Ft Flat to 6 12 1 0 Over 11 12 to 12 12 4 0 6 12 to 7 12 1 25 Over 12 12 to 14 12 5 0 Over 7 12 to 8 12 1 5 O...

Page 12: ...ded through the brackets and tighten nut to complete the storm collar assembly see Figure 2 22 Make sure the collar is tight against the pipe section Slide the assembled storm collar down the pipe sec...

Reviews: