The Priority Shield option allows a zone to ignore other 

priorities from other zones. 

A priority set to none will have no priority and will be 

overridden by all other zone priorities.

Priority 1 is a timed priority of 60 minutes, generally used 

for DHW.

Priority - 

This option allows the user to set a priority on a zone(s) over other 

zone(s). Priorities range from 1 (highest) to 7 (lowest). Higher priorities will lock 

out lower priorities until the demand has been satisfied. Multiple zones can be 

given the same numbered priority. 

Mode - 

This option allows you to select between Air, Floor and Dual sensor 

modes. If you are setting your Thermostat as a DHW demand the thermostat 

will automatically configure your sensor to a digital Aquastat.

Air

 

Thermistor within the thermostat sensing temperature 

providing feedback for the specific room or zone being 

controlled by the thermostat.

Floor

 

Sensor temperature providing feedback from the 

floor surface to the thermostat. This mode will run the 

thermostat on floor temperature only. Aux sensor will 

automaically be set to floor.

Only available when heating modes are 

the primary function. Must have floor sensor 

connected.

Floor Mode: Differential

When in floor mode, the differential option is set to allow 

a differential around the target to reduce the chances 

of short cycling.

Ex. A differential of 4°F is 2°F above the setpoint and 2°F 

below the setpoint.

Special Functions

ATHM-0000

Stat Type

Demand Type

Priority

THM  Mode

Aux Sensor

Room Offset

Fancoil Setup

Heat Only

Low

None

Air

Floor

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Room Offset

Fancoil Setup

4-Pipe Geo

Default Setup

Password

Air

Floor

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Differential

Room Offset

Fancoil Setup

4-Pipe Geo

Default Setup

Floor

Floor

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Floor Min

Floor Max

Room Offset

Fancoil Setup

4-Pipe Geo

Dual

Floor

70°

80°

-20°

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Room Offset

Fancoil Setup

4-Pipe Geo

Default Setup

Password

Air

Floor

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Differential

Room Offset

Fancoil Setup

4-Pipe Geo

Default Setup

Floor

Floor

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Floor Min

Floor Max

Room Offset

Fancoil Setup

4-Pipe Geo

Dual

Floor

70°

80°

-20°

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Room Offset

Fancoil Setup

4-Pipe Geo

Default Setup

Password

Air

Floor

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Differential

Room Offset

Fancoil Setup

4-Pipe Geo

Default Setup

Floor

Floor

OFF

Special Functions

ATHM-0000

THM  Mode

Aux Sensor

Floor Min

Floor Max

Room Offset

Fancoil Setup

4-Pipe Geo

Dual

Floor

70°

80°

-20°

OFF

Summary of Contents for THM-0600

Page 1: ...HBX Control Systems Inc Installation Manual THM 0600 Touch Screen Programmable Thermostat Version 1 0 0 THM 0600...

Page 2: ...cessor based controller and as such is not to be regarded as a safety limit control Please consult and install the heating or cooling appliance in accordance with the manufacturer s recommendations TA...

Page 3: ...HM 0600 has two external sensor inputs multiple heating cooling modes and can function as a digital setpoint aquastat Some features of the THM 0600 are Dual stage heating or cooling P I D algorithm La...

Page 4: ...nsulated 1 2 3 4 1 2 External Room Sensor 3 4 Aux Sensor TH Communication Power from ZON 0600 Use a screwdriver to gently pop the front cover off from the top of the thermostat and then remove the fro...

Page 5: ...t a location for your system on the ThermoLinx app in settings 100 9 41 AM City App Degrees Contractor Code Key 12345 Location Time Zone Alaska 9hrs GMT Calgary C F Paci c 8hrs GMT Central 6hrs GMT Mo...

Page 6: ...Outdoor 47 F Zone 1 LIVING ROOM Floor 70 F Target 72 F 72 0 F 10 00am Special Functions Type Heat Only Backlight View Auto Room Offset 0 F Setbacks Geo Mode Outdoor 47 F No settings will be able to be...

Page 7: ...at and Cool Low None Air Floor 0 Special Functions ATHM 0000 Stat Type Demand Type Priority THM Mode Aux Sensor Room Offset Fancoil Setup 2 Stage Heat Low None Air Floor 0 Special Functions ATHM 0000...

Page 8: ...Priority THM Mode Aux Sensor Room Offset Fancoil Setup 2 Cool with Heat Low None Air Floor 0 Special Functions ATHM 0000 Stat Type Demand Type Priority THM Mode Aux Sensor Room Offset Fancoil Setup 2...

Page 9: ...erential option is set to allow a differential around the target to reduce the chances of short cycling Ex A differential of 4 F is 2 F above the setpoint and 2 F below the setpoint Special Functions...

Page 10: ...rds internal sensor uses external Outdoor Uses external sensor to display outdoor temperature RM Ave Averages auxiliary sensor and internal sensor or optional external room sensor Floor Ave Averages a...

Page 11: ...rd Air Floor 0 OFF Fancoil Setup Fan ON Demand Zone ON Demand Temp Average Stage Delay Damper Mode OFF OFF None 15 mins OFF Fancoil Setup Fan ON Demand Zone ON Demand Temp Average Stage Delay Damper M...

Page 12: ...N C 1st stage is radiant and the second stage is utilizing a normally closed damper This option will require to use the next corresponding zone output to accommodate for the second stage damper This...

Page 13: ...o default Default Setup Restores the thermostat to factory default settings or previously saved settings Selecting this option allows you to change the password No Password will remain the same Yes Th...

Page 14: ...ch schedule event Heating Temperature Red Select the heating temperature and adjust accordingly for each schedule event Setup Menu Schedules Weekday Settings Weekend Settings Mode Away Settings Humidi...

Page 15: ...o select a cool target when away mode is enabled Heating Cooling Target The chosen setpoint for heating and cooling zones Targets will be accessible in relation to the thermostat type chosen Mode This...

Page 16: ...egardless of whether the thermostat is calling for heating or cooling INT This setting will set the ON OFF time for the intermittent fan Ex The fan will come on for 15 min every 2H Set Int Fan On 15 m...

Page 17: ...s Fan Settings Backlight Degrees ON Bright F Mode Away Settings Humidity Humidity Settings Fan Settings Backlight Degrees Heat OFF ON Bright F Setup Menu Mode Away Settings Humidity Humidity Settings...

Page 18: ...NOT CONNECT POWER HERE INT ROOM EXT ROOM HBX TH TH Fancoil R W Y G C Fancoil Heat Cool Pump DO NOT CONNECT POWER HERE GR POWER 120 17 N L 16 15 0 4 3 I TT 1 0 6 5 I TT 2 5 TH 1 10 9 6 5 12 11 6 5 14 1...

Page 19: ...N 2 N 11 12 H ZN 3 N 13 14 H ZN 4 N 5 6 H ZONE POWER 5A 5A 5A 5A 1 2 1 1 W R Fancoil Outputs 0 8 7 I TT 3 Demand Outputs 1 18 17 1 Thermostat Signal Communication Fancoil Outputs EXT THM TH 2 TH 3 TH...

Page 20: ...WER 120 17 N L 16 15 0 4 3 I TT 1 0 6 5 I TT 2 5 TH 1 10 9 6 5 12 11 6 5 14 13 6 5 16 15 6 2 Y G 20 19 2 X 21 2 5A 1 PUMP 1 1 2 1 1 PUMP 2 3 4 1 5A HBX ZON 0600 Zone Control N ZN 1 7 8 H N 9 10 H ZN 2...

Page 21: ...o operate due to P I D algorithm Verify wiring on the ZON 0600 module Check priorities settings in special functions Check the mode settings Temperature not displaying correct value If it is showing d...

Page 22: ...nually check in thermostat s Ensure zone modules are linked System is not connected to the internet Thermostat settings not all displayed on the ThermoLinx App Contact HBX Technical Support for contac...

Page 23: ...on repair or replacement The foregoing warranties and remedies are exclusive and in lieu of all other warranties expressed or implied either in fact or by operation of law statutory or otherwise inclu...

Page 24: ...V1 02 Toll Free Technical Support 1 855 410 2341...

Reviews: