19
ISSUE
POSSIBLE CAUSES & RESOLUTIONS
Blank Screen
• Check the ZON-0600 power
• Check wiring polarity between the THM-0600
and ZON-0600 module.
• Ensure zones 1 and 3 damper/4-pipe is set
correctly.
Stage 2 won’t
come on
• Check stage delay in fancoil setup for
proper time.
• In special functions ensure you have
selected correct thermostat type.
Demand not
coming on
• Demands may take up to 5 minutes to
operate due to P.I.D algorithm.
• Verify wiring on the ZON-0600 module.
• Check priorities settings in special functions.
• Check the mode settings
Temperature
not displaying
correct value
• If it is showing dash lines ensure that the
proper thermostat mode is selected in
special functions.
• Ensure aux sensor(s) is wired correctly.
• Make sure the external room dipswitch on
the board is in the correct position.
Target
changing
• Check the schedule
• If you’re in auto changeover, then the
target can change to either heating target
or cooling target based on actual room
temperature.
TROUBLESHOOTING GUIDE