SYSTEM SETUP
SYNC CODE: ABCD-1234
1) ZONE SETUP
2) FANCOIL SETUP
3) STAGE DELAY
3
m
Fancoil Setup
This setting takes you to the Fancoil Setup Menu.
Fancoil Setup: Fan On Demand
This option will turn the fan on with any fancoil
demand
FANCOIL SETUP
1) FAN ON DMD NO
2) ZONE ON DMD NO
3) TEMP AVE
NONE
4) FAN MODE
OFF
Fancoil Setup: Zone On Demand
This option will turn the zone pump on with any
fancoil demand
FANCOIL SETUP
1) FAN ON DMD NO
2) ZONE ON DMD NO
3) TEMP AVE
NONE
4) FAN MODE
OFF
Fancoil Setup: Temperature Averaging
This option will average the temperature between
thermostats, when that average falls below or
above the setpoint, depending on if it’s in heating
or cooling, then the thermostat will make a call for
heating or cooling on the fancoil.
FANCOIL SETUP
1) FAN ON DMD NO
2) ZONE ON DMD NO
3) TEMP AVE
NONE
4) FAN MODE
OFF
Fancoil Setup: Fan Mode
OFF
: Indicated Fan is off
ON
: Enables the fan to run constantly, regardless
of whether the thermostat is calling for heating or
cooling
INT
: This setting will set the ON/OFF time for the
intermittent fan
Ex: The fan will come on for
15
min every
2H
. Set
(Int Fan On:
15
min) & (Int Fan Off:
2H
)
FANCOIL SETUP
1) FAN ON DMD NO
2) ZONE ON DMD NO
3) TEMP AVE
NONE
4) FAN MODE
OFF
Fan Mode INT: Intermittent Fan On
Sets the amount of time the fan will operate. Only
applicable when Fan Mode is set to
INT
.
FANCOIL SETUP
1) FAN ON DMD NO
2) ZONE ON DMD NO
3) TEMP AVE
NONE
4) FAN MODE
INT
5) INT FAN ON
2
m
6) INT FAN OFF
1
H
Fan Mode INT: Intermittent Fan Off
Sets the amount of time that must pass before the
fan can come on again. Only applicable when
Fan Mode is set to
INT
.
FANCOIL SETUP
1) FAN ON DMD NO
2) ZONE ON DMD NO
3) TEMP AVE
NONE
4) FAN MODE
INT
5) INT FAN ON
2
m
6) INT FAN OFF
1
H