![HBM MP60DP Operating Manual Download Page 18](http://html.mh-extra.com/html/hbm/mp60dp/mp60dp_operating-manual_2111904018.webp)
18
PME
−
MP60DP
HBM
A0623-6.1 en/de/fr
6.3.2 Outputs (from the PLC to MP55IBS)
Limit values
Limit values are displayed in the same format as the measured values (16 bit
integer, 32 bit integer or floating format). The operating direction and
hysteresis remain unchanged and are set via the operating panel or the
CAN
−
bus.
Control word
Bits
Name
Meaning
0
ZERO
0
−
1 autom. triggers zeroing
1
TAR
0
−
1 triggers taring
2
SHUNT
SHUNT ON / OFF
3
res
reserved
4
CLRMAX
0
−
1 clears the MAX peak value store
5
CLRMIN
0
−
1 clears the MIN peak value store
6
HOLDMAX
1: freeze MAX peak value store
7
HOLDMIN
1: freeze MIN peak value store
8
PAR1
parameter set selection bit 1
9
PAR2
parameter set selection bit 2
10..15
res
reserved
Tab 6.7:
Contents of control word