The targeted operation of the required control bits in the control word allows
you to secure all the functions not required against accidental operation in the
event of an error; otherwise, for example, the zero point set could be lost.
If you are using older parameter assignment tools the parameter values will
have to be converted to decimal or hexadecimal values:
Octet Bits Parameter name
Available values
Default
Meaning
0
0..7
reserved
0
0
do not change
1)
1
−
2
all
Diagnosis
0 = disabled
0xffff = released
released
release of external
diagnosis
3
all
Data format
0 = integer 16 bits
1 = integer 32 bits
2 = floating point
integer 16 bits
defines the coding
format for measured
values
5
0
Zeroing control
bit
0 = disabled
1 = released
disabled
releases function for
control of output
control word
5
1
Taring control bit
0 = disabled
1 = released
disabled
releases function for
control of output
control word
5
4
Control bit
Delete maximum
0 = disabled
1 = released
disabled
releases function for
control of output
control word
5
5
Control bit
Delete minimum
0 = disabled
1 = released
disabled
releases function for
control of output
control word
5
6
Control bit
Hold maximum
0 = disabled
1 = released
disabled
releases function for
control of output
control word
5
7
Control bit
Hold minimum
0 = disabled
1 = released
disabled
releases function for
control of output
control word
4
0
−
1
Parameter set
control bits
0 = disabled
3 = released
disabled
releases function for
control of output
control word
Tab 6.2:
Contents of the parameter assignment message
1)
changed by your parameter assignment tool in certain circumstances