![HBM MP07 Operating Manual Download Page 7](http://html1.mh-extra.com/html/hbm/mp07/mp07_operating-manual_2111883007.webp)
7
PME-MP60/MP07
A0616-13.4 en
HBM
Symbol:
Meaning:
CE mark
The CE mark enables the manufacturer to guarantee that the product com-
plies with the requirements of the relevant EC directives (the declaration of
conformity is available at http://www.hbm.com/HBMdoc).
Working safely
Error messages should only be acknowledged once the cause of the error is
removed and no further danger exists.
The device complies with the safety requirements of DIN EN 61010 Part 1
(VDE 0411 Part 1).
The device must be mounted on a support rail connected to grounded con-
ductor potential. Both the support rail and the MP60/MP60DP module must be
free of paint, varnish and dirt at the point of installation.
To ensure adequate immunity from interference, the bus cables (CAN and for
MP60DP, Profibus DP) must be shielded, twisted
−
pair lines. The transducer
cables must also be shielded. To ensure adequate immunity from interfer-
ence, use Greenline shielding only (conncect the shield of the transducer
cable to the plug housing).
The cables of the digital inputs and outputs of the MP60/MP60DP should not
be longer than 30 m or should they be routed outside the building where the
system is located. Otherwise proper functioning of the device cannot be guar-
anteed. The effects of strong electromagnetic fields or lightning strike could
result in damage to the instrument.
When connecting cables (fitting and extracting terminals), measures must be
taken to prevent electrostatic discharge which could damage the electronics.
The MP60/MP60DP module needs to be operated with a separated extra
−
low
voltage (18...30 V DC supply voltage), which usually supplies one or more
consumers within a control cabinet.
Should the equipment be operated on a dc voltage network
1)
, additional pre-
cautions must be taken to discharge excess voltages.
1)
Distribution system for electrical energy with greater physical expansion (over several control cabinets, for
example) that may possibly also supply consumers with high nominal (rated) currents.
Summary of Contents for MP07