1: Check System
‘PFC-Hi Error’
Wire the pump to the ‘filter’ relay and set timers in the automation system as desired.
Keep in mind, the EcoStar must be powered down for at least 1 minute every 24 hours.
Page 5
Step 1C
Note: This solution will cause a ‘Bridge Comm Error’ on the controller. This expected error indicates that the
pump is not communicating while powered down; this error will clear when pump’s power is restored. Please
inform customer prior to employing this solution.
When connected to Hayward Automation, automatically clear error daily by wiring
the pump to the load side of the ‘filter’ relay (do not disrupt low voltage wiring):