4. The Aqua Plus 16v can be programmed to accommodate spillover if desired.  Note that spillover operation

will be automatically suspended whenever the spa filter pump is turned on.

5. The chlorinator cell must be installed in the pool plumbing.  If spillover is enabled, then the Aqua Plus 16v

can chlorinate both the pool and spa (during spillover operation).  Otherwise, the Aqua Plus 16v will only
chlorinate the pool and the spa sanitization will have to be handled manually.

6. If any water feature or pressure side cleaner boost pumps are used, be sure to enable the “interlock”

feature (see “Configuration Menu” for details) to ensure that the pumps operate only when the “Pool
Filter” pump is on and the system is in the “pool only” operating mode.

7. The plumbing diagram on page 9 is intended to be used as a general guideline and is not a complete

plumbing schematic for the pool.

8. When using the wireless spa-side remote control (AQL2-SS-RF), the “POOL” button will position the

valves for Pool mode and the “SPA” button will position the valves for Spillover mode.

“Dual Equipment - Shared Heaters” for Pool/Spa configuration

These systems have 2 complete sets of equipment (filter pump, filter) and shared heaters.  Refer to the diagram
below:

Some important notes regarding the Aqua Plus 16v control of Dual Equipment Pool/Spa systems with shared
heaters:

In the Pool/Spa Config., select:  

Pool/Spa Setup

Pool and Spa-Dual

  

Heaters

Shared

1. When dual equipment is selected:

a. The “filter” pump automatically is renamed “Pool Filter” and can not be changed.  The pool filter

can be a one, two or variable pump.

b. The “Aux1” output is automatically renamed “Spa Filter”, its function is set to “Timeclock” and the

Interlock feature is forced to “Disabled”.  None of these can be changed.  The spa filter can be a
one, two or variable pump.

c. The Valve3 configuration menu is disabled.
d. The heater(s) will be dedicated to the spa whenever the spa filter is on and the spa temperature

setting is not off.

2. The water sensor should be installed on the pool loop prior to the heater(s) and will display the pool

temperature whenever the “Pool Filter” pump is running.

3. The dual equipment spa sensor should be installed on the spa loop prior to the heater(s) and will display

the spa temperature whenever the “Spa Filter” pump is running.

10

33

speed are controlled by commands sent to the VSP.  Note: Up to 6 Lights/Aux outputs can be
configured as VSP relays.

Lights Interlock

If enabled, this feature will override the function (Manual On/Off, Countdown Timer, Timeclock)

selected above and turn the lights relay off when:  filter pump is off, first 3 minutes of filter pump

operation (allows the pump to prime and get water flowing), when the pool/spa suction return valves

are in any position other than “pool only”, or for the first 3 minutes after solar turns on (allows air in

the solar panels to be purged).  Interlock is not available for solar, low speed filter pump, dimmer,
group, super chlorinate, or pH dispense functions.

Lights Group

The Lights Group function allows the user to perform multiple tasks with a single push of the “Lights”

button. When setting up a Group function, refer to page 22 for specific programming information.

There are two Group menus; the first menu determines how the group command will be initiated

(Manual On/Off, Countdown Timer, or Timeclock) and the second menu selects the desired functions

and their respective control parameters.

When activating Group functions, be aware that the most recent Group function that is initiated will
override any previous Group function.

Lights External Input Interlock

When Lights External Input Interlock is enabled, the lights output will be forced off when the external
input is active.  This will have precedence over freeze protection.  Lights External Input Interlock is not
available for solar, low speed filter pump, dimmer, group, super chlorinate, or pH dispense functions.

Lights Freeze Protection

This function helps protect equipment that is wired to the lights relay against freeze damage.  If Freeze
Protection is enabled and the AIR temperature sensor falls below the selected freeze temperature
threshold, the Pro Logic will energize the lights relay.  IMPORTANT:  this only enables operation of the
lights relay during freeze--see the “Filter Pump Config.” menu to enable freeze protection for the main
circulation system. Freeze Protection is not available for low speed filter pump, dimmer, group, super
chlorinate or pH dispense functions.

Lights Pump Speed

This is the speed of the filter pump when the Lights output is on.  The default selection is “Settings
Menu”.  This is the speed of the pump that has been selected in the Settings Menu for normal filter
operation. If an alternate speed is desired when the Lights output is on, push “+” or “-” and select from
“Filter Lowest” to “Filter Highest” in 5% increments.

NOTE: The configuration parameters for all Aux outputs are the same as shown below for Aux1.  PS-4: Aux1 and Aux2. PS-8:

Aux1 through Aux6. PS-16: Aux1 through Aux14. Also note that for the PS-16, Valves7, 8, 9 and 10 are turned On/Off with the

control function selected for Aux7, 8, 9, and 10, respectively.

POOL

FILTER

ELECTROLYTIC

CELL

FLOW

SWITCH

POOL FILTER

PUMP

VALVE 1

VALVE 2

VALVE 3

In from POOL

Out to SPA

Out to POOL

In from SPA

SPA

TEMPERATURE

SENSOR

SPA

FILTER

SPA FILTER

PUMP

HEATER

HEATER

SOLAR BOOST

PUMP

SOLAR

VALVE

CHECK

VALVE

SOLAR

TEMPERATURE

SENSOR

CHECK

VALVE

Summary of Contents for Aqua Plus 16v PL-PLUS-16V

Page 1: ...ach wireless remote wireless channel maintenance menu pH calibration wizard clean probe wizard timers menu pool filter 1 or hi speed 1 pool filter 2 or lo speed 1 pool filter 3 or hi speed 2 pool filt...

Page 2: ...ytotheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Page 3: ...tion 7 Optional ValveActuators 7 3 Plumbing Standard Pool Spa Configuration 8 Dual Equipment Pool Spa Separate Heaters 9 Dual Equipment Pool Spa Shared Heaters 10 Turbo Cell 11 Flow Switch 11 4 Electr...

Page 4: ...product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation specialist should be con...

Page 5: ...olar thermostat settings Chlorinatorsettings DayandTime Timers Menu Timeclockand orCountdowntimersettings Heater Checkout FollowtheseinstructionstoverifythattheAquaPlus16visproperlycontrollingtheheate...

Page 6: ...the pool per manufacturer s instructions Thisensuresaquick troublefreetransfertotheAquaPlus16vsystem 40 Reset ColorLogic to Default Press Are you sure to proceed ColorLogic reset Confirmed Initiate re...

Page 7: ...peciallyimportantforretrofitinstallationtoolderpoolswhereallofthe chlorineaddedtothepoolovertimeisendingupassalt Ifthelevelislow determinethenumberofgallonsinthe pool and add salt according to the cha...

Page 8: ...4 3 0 1 4 3 5 1 6 2 5 1 6 4 5 2 0 5 5 2 5 8 0 3 6 6 5 2 9 9 0 4 1 7 0 3 2 9 5 4 3 7 5 3 4 10 0 4 5 2 0 91 1 3 91 2 0 91 2 8 1 3 2 3 1 1 1 7 1 1 2 7 1 2 3 3 1 5 3 7 1 7 5 3 2 4 4 3 2 0 4 7 2 1 6 3 2 8...

Page 9: ...r Valve3 Name Waterfall Push to access Valve3 options Rotates between Manual On Off default Countdown Timer Timeclock Solar In floor Cleaner Group and Super Chlorinate Move to previous next configurat...

Page 10: ...theAQL2 BASE RFforallAQL2wirelessremotecontrols Toinstallthebasestation removetheknockout on the upper left side of theAqua Plus 16v main control unit insert the base station and then tighten the nut...

Page 11: ...sing kit Aux1 Relay This feature allows the user to select either Standard default Dimmer ColorLogic or VSP type relay for the Aux1 output The optionalAQL DIM dimmer kit must be installed if Dimmer is...

Page 12: ...ff countdown timer and timeclock functions Move to next menu item Rotates between Manual On Off default Countdown Timer Low Speed Filter Timeclock Solar Low Speed Spa Filter Group Super Chlorinate and...

Page 13: ...et water flowing when the pool spa suction return valves are in any position other than pool only or for the first 3 minutes after solar turns on allows air in the solar panels to be purged Interlock...

Page 14: ...e Aux relays If pool lights are wired to the lights relay some options including Solar function Low Speed of a 2 Speed Filter Pump Lights Interlock and Lights Freeze Protection are not applicable and...

Page 15: ...e between Open and Closed default Move to next menu item or previous next configuration menu External Input The external input device can either be normally open or normally closed In this menu select...

Page 16: ...ove to next menu item Move to next menu item if Solar is enabled if Solar is enabled Allow Low Speed Disabled Toggle between Enabled and Disabled default Move to next menu item or previous next config...

Page 17: ...ext configuration menu if Heater1 is enabled if Heater1 is enabled if Heater1 is enabled display for Heater2 if Heater2 is enabled Heater1 Name Gas Heater Rotates between all available names Move to n...

Page 18: ...Lowest Speed 10 Highest Speed 100 Rotates between 1 speed default 2 speed and variable speed options Toggle between Enabled default and Disabled Freeze Protection Toggle between high speed default and...

Page 19: ...irst 3 minutes of operation anytime the pump has been off for more than 30 seconds Set highest speed from 20 to 100 default Flow Monitor This feature will help protect the filter pump from damage due...

Page 20: ...ver the Pool Spa valves are turning The pump will NOT shut off when the heater has Cooldown enabled and is either on or in the Heater Cooldown mode Filter Config to view change Filter Name Pool Filter...

Page 21: ...actuators should be connected to the Pro Logic Pressing the POOL SPAbutton on the display keypad will allow the homeowner to alternate between pool and spa operation If Pool and Spa Dual is selected...

Page 22: ...ically locks after 2 minutes of no buttons being pressed to prevent unauthorized people from changing the control logic inadvertently and possibly damaging the pool equipment or causing a call back to...

Page 23: ...while the Group is running will make the Group release the alternate setpoint control and revert back to the normal heater setting Any changes that are made at that point will affect the normal heater...

Page 24: ...d dim the patio lights turn on the music etc all at the same time This convenient feature is offered on allAux buttons bothValve buttons and the Lights button TheAqua Plus 16v can be programmed to con...

Reviews: