OPERATING INSTRUCTIONS 

 

Instruct all employees in the use of this Emergency Eyewash. Personnel should be assigned to 
check eyewash liquid level daily. 

 

STEP 1: 

Lead patient to nearest eyewash station.  Seconds can make the difference in 
preventing serious eye injury. 

STEP 2: 

Pull yellow eyewash arm firmly. Eyewash arm will drop to activate eyewash. 

STEP 3: 

Lower head until eyes enter eyewash stream. Use thumbs and forefingers to hold 
eyelids open. Flush for 15 minutes. 

STEP 4:  

Seek qualified medical attention immediately. 

 

MAINTENANCE INSTRUCTIONS 

 

NOTE: 

Customer must provide an inspection tag and maintain a record of inspections 
dates and type of maintenance performed (i.e.

 

adding Sterile Antimicrobial 

Preservative Model 9082, etc.) 

STEP 1:

 

Self-contained eyewash equipment shall be visually checked to determine if 
flushing fluid needs to be changed or supplemented. See STEP 3 for additional 
information regarding activated units. 

Frequency of inspection: 

Depending on environmental conditions, visual 

inspections should be performed on either a daily, weekly or monthly basis as some 
water loss will occur due to natural evaporation process.  

 

STEP 2:

 

Take proper precautions to help prevent the growth of potentially harmful bacteria in 
eyewash tanks.  We recommend 

either

 of the following procedures: 

 

NOTE:

 

Disconnect Model 7501T/7501T240 from power source before performing 
maintenance. 

   

 

Procedure A:

 Use suitable Sterile Antimicrobial Preservative Model 9082 to help 

prevent the growth of bacteria in eyewash tank.  Eyewash tank should be drained, 
flushed and refilled with clean potable water and Sterile Antimicrobial Preservative 
Model 9082 as directed by the preservative’s manufacturer. 

 

PROCEDURE B: 

Drain, flush and refill portable units with clean potable water at 

least once every week. Thoroughly cleanse tank at least once every month. 

NOTE: 

Acanthamoeba survive mild chlorination and are commonly found in tap 

water. Sterile Antimicrobial Preservative Model 9082 will prevent the growth of 
Acanthamoeba.  Hot water, 158

F (70

C) or hotter will destroy Acanthamoeba but 

must be allowed to cool prior to use in eyewash units. 

 

STEP 3:   

After activating units for any reason ensure the following steps are implemented: 

 

 

 

A. 

Refill tank with potable water to the watermark line.

 

B. 

If water is discharged for any reason – follow Procedure 1 or Procedure 2 of                             

__

Step 2 above to ensure that water quality is maintained.

 

 

Summary of Contents for 7501

Page 1: ...ts except upon written authority from HAWS Sparks Nevada HAWS will not be liable for any damages caused by defective materials or poor workmanship except for replacements as provided above Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated except that of title with respect to any of the products or equipment sold hereunder and that HAW...

Page 2: ...ONNECTIONS reference manual supplied with heating blanket Model 7501T 120VAC 60 Hz 1 38A Requires a three prong outlet and is supplied with a heavy duty 8 foot power cord with GFCI plug Unit is suitable for installation and use in NEMA TYPE 3R areas Must be used with NEMA TYPE 3R certified covered outlet not supplied DURING POTENTIAL FREEZING PERIODS INSURE THAT UNIT IS CONNECTED TO A CONTINUOUS P...

Page 3: ...e lowered position See Installation Drawings pages 7 and 8 of 8 Filled eyewash unit is heavy approximately 80 pounds Wall bracket anchors Quantity 3 not supplied must be strong enough to support the filled eyewash and the weight of a worker leaning on eyewash STEP 4 Fill up to fill line see important note above Requires 8 75 gallons max of water make sure that no debris or contaminants of any kind...

Page 4: ...ome water loss will occur due to natural evaporation process STEP 2 Take proper precautions to help prevent the growth of potentially harmful bacteria in eyewash tanks We recommend either of the following procedures NOTE Disconnect Model 7501T 7501T240 from power source before performing maintenance Procedure A Use suitable Sterile Antimicrobial Preservative Model 9082 to help prevent the growth o...

Page 5: ... reached b Make sure unit is level from front to back and left to right 5 Eyewash flows for less than 15 minutes 5 Fill water level in eyewash tank even with water fill line indicated on side of unit 6 Excessive water loss 6 Check unit for leaks Some loss due to evaporation is normal 7 Heater doesn t turn on Model 7501T 7501T240 7 a Not plugged in or no power to outlet Check GFCI plug 7501T only a...

Page 6: ...BY ECN NO PAGE DATE DATE ECN REVISED PER CHKD Haws Corporation All Rights Reserved HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation C R MODEL S 1455 KLEPPE LANE SPARKS NEVADA 89431 775 359 4712 FAX 775 359 7424 E MAIL HAWS HAWSCO COM WEBSITE WWW HAWSCO COM ITEM DESCRIPTION THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION CONTINUED PRODUCT IMP...

Page 7: ...2mm DO NOT EXCEED WATER FILL LINE REFER TO INSTALLATION INSTRUCTIONS IN OPERATION AND MAINTENANCE MANUAL FOR PROPER FILLING PROCEDURES 4 4 MODEL 7501 SHOWN FOR MODELS 7501T 7501T240 WITH HEATED BLANKET SEE SHEET 2 OF 2 FLOOR LINE MOUNTING DETAILS 33 53 838mm 1346mm FLOW PATTERN NOTES 1 WHEN INSTALLING THIS UNIT LOCAL STATE OR FEDERAL CODES SHOULD BE ADHERED TO FOR INSTALLATION DIMENSIONS LOCATIONS...

Page 8: ...E SJ SJE SJO SJOO SJT SJTO SJTOO SO SOO ST STO OR STOO AND HAVE A TYPE LETTER SUFFIX OF W W A OR OUTDOOR 10 THE CORD SET SHALL BE MIN 6 FT IN LENGTH AND MIN 18 AWG SIZE FOR FLEXIBLE POWER SUPPLY CORD 11 LISTED STRAIN RELIEF BUSHING SUITABLE FOR CORD SET SIZE AND OUTDOOR USE SHALL BE USED 12 ALL MODELS MUST HAVE A GROUND FAULT PROTECTION DEVICE 30mA GFEPD FOR HEAT TRACE ELECTRICAL CURRENTS MAY BE I...

Reviews: