![Haws 7501 Nstallation, Operation & Maintenance Instructions Download Page 2](http://html.mh-extra.com/html/haws/7501/7501_nstallation-operation-and-maintenance-instructions_2110157002.webp)
03/18
Model 7501/7501T/7501T240
Page 2 of 8
CAUTION : A GROUND FAULT DEVICE MUST BE USED WITH THIS HEATING DEVICE.
ATTENTION : CE PRODUIT DOIT ÊTRE UTILISÉ AVEC UNE PROTECTION DE MISE À LA
TERRE.
RECOMMENDED TOOLS:
Three 1/4" diameter anchors suitable for supporting filled eyewash
(approximately 80 pounds), and tools needed to install these anchors.
LOCATION OF UNIT:
The Model 7501/7501T/7501T240 eyewash units should be installed in
close proximity to potential accident areas. It should be clearly identified, free from obstructions
and easily accessible.
IMPORTANT: Model 7501 eyewash units (non-insulated) shall be
protected from freezing. Models 7501/7501T/7501T240 shall not have internal
temperatures exceeding 38
⁰
C (100
⁰
F) and shall not be exposed to ambient temperatures
exceeding 38°C (100°F). Be careful of direct sunlight.
ELECTRICAL CONNECTIONS: (reference manual supplied with heating blanket)
Model 7501T
– 120VAC, 60 Hz, 1.38A. Requires a three-prong outlet and is supplied with a
heavy-duty 8 foot power cord with GFCI plug. Unit is suitable for installation and use in
NEMA/TYPE 3R areas. Must be used with NEMA/TYPE 3R certified covered outlet (not
supplied).
DURING POTENTIAL FREEZING PERIODS INSURE THAT UNIT IS
CONNECTED TO A CONTINUOUS POWER SUPPLY.
Model 7501T240
– 240VAC, 50/60 Hz, 0.64A. Requires a 240VAC outlet and is not supplied
with a power cord which must be installed by the user. Unit is suitable for installation and use
in NEMA/TYPE 4 areas. Power connection to be per local code using flexible conduit or cable
rated NEMA/TYPE 4 – no rigid connection permitted.
MUST BE PROTECTED BY A Class A
GROUND FAULT CIRCUIT INTERRUPTER (GFCI).
DURING POTENTIAL FREEZING
PERIODS INSURE THAT UNIT IS CONNECTED TO A CONTINUOUS POWER SUPPLY.
AMBIENT TEMPERATURE RATINGS:
MODEL 7501:
60°F (16°C) TO 100° (38°C)
MODEL 7501T:
-22°F (-30°C) TO 100°F (38°C)
MODEL 7501T240:
-30°F (-35°C) TO 100°F (38°C)