10/08
Model H1001.8/H1001.8HPS
Page 5 of 7
MAINTENANCE
Step 1:
The condenser fins on chiller should be periodically cleaned with brush, air hose
or vacuum cleaner. Care should be taken not to bend or deform the condenser
fins.
Step 2:
The chiller temperature control is factory set for 50° F water under normal
conditions. For colder water, adjust control clockwise. For warmer water, turn
counterclockwise. Remove front chiller panel for access to temperature control.
After adjustment allow unit to cycle off before checking outlet water temperature.
TROUBLESHOOTING
PROBLEM
REPAIR CHECKLIST
1. Insufficient bubbler flow.
1a.
Check that inlet screwdriver stop valve is
in wide-open position.
b.
Verify minimum 30 psi flowing supply
pressure.
c.
Clean strainer. See 5874 Valve Manual.
d.
Adjust valve to increase flow. Use front
adjust screw or see 5874 Valve Manual.
2. Water too warm or cold.
a.
Adjust chiller temperature control,
clockwise for colder water.
© 2006 Haws
®