1. Turn off the power.
2. Install the controller mechanically.
3. Pull out the quick couplings.
4. Connect the cables to the quick couplers according to the description or connection diagram:
4.1.
Connecting the limit switch for opening and closing.
The controller works as a standard with electromagnetic switches
supplied with 5Vdc voltage and with 5Vdc voltage output signal (PNP type).
The limit switch for opening and closing is used to precisely stop the gate in the closed or
open position. Adjust their position so that the gate opens and closes accurately.
24
+5VDC
– „+” power supply for sensors (yellow wire),
16
OL
— signal from the opening limit switch (green wire),
17
CL
— signal from the closing limit switch (red wire),
23
COM
— power supply for sensors "-" (white wire).
4.2.
Connecting photocells.
The infrared barrier is an essential security element that must be connected to the
controller. It prevents the gate from hitting a vehicle, person or object in its light. Photocells are
necessary for the correct operation of the device and ensure safety. It is required to connect a
safety curtain or other additional protection against crushing in the door clearance. They must be
connected in series with the photocells
Photocells
12
+24VDC
– plus power for photocell
13
COM
– minus power for photocell
13
COM
– photocell COM output
14
FOTO
– NC contact of the photocell
The power supply of the 24V connector is <450mA, therefore make
sure that the total power load does not exceed this current value. An
exemplary photocells connection diagram is shown in fig. 2.
4.3.
Connection of manual control.
Connection of the manual control should be made with a 2x 0.5mm cable (the cable type
should be in accordance with CEI 20-22; CEI EN50267-2-1 standards), the maximum length of the
manual control cable depends on its electrical parameters, therefore it should be assumed the
following rule that with the required cable length, its resistance should not exceed 100ohm. As a
standard, the use of a cable with a cross-section of 0.5 mm and a length of not more than 20 m is
sufficient for the correct operation of the controller, for required greater distances, 4x0.5 (mm)
cables can be used by connecting the wires in parallel - in pairs, or by increasing the cross-section
of the cable (2x 1mm).
15
SBS – bell button
18
COM
Next, make the electrical connections of the connector on the left side
as shown in fig. 2.