background image

1. Turn off the power.
2. Install the controller mechanically.

3. Pull out the quick couplings.
4. Connect the cables to the quick couplers according to the description or connection diagram:

4.1.

Connecting the limit switch for opening and closing.

The   controller   works   as   a   standard   with   electromagnetic   switches

supplied with 5Vdc voltage and with 5Vdc voltage output signal (PNP type).

The limit switch for opening and closing is used to precisely stop the gate in the closed or

open position. Adjust their position so that the gate opens and closes accurately.
 

  24 

+5VDC

 – „+” power supply for sensors (yellow wire),

                               

16

 OL

 — signal from the opening limit switch (green wire),

                               17

 CL

 — signal from the closing limit switch (red wire),

                               23 

 COM

 — power supply for sensors "-" (white wire). 

4.2.

Connecting photocells.

The   infrared   barrier   is   an   essential   security   element   that   must   be   connected   to   the

controller. It prevents the gate from hitting a vehicle, person or object in its light. Photocells are
necessary for the correct operation of the device and ensure safety. It is required to connect a

safety curtain or other additional protection against crushing in the door clearance. They must be
connected in series with the photocells

Photocells

12

 +24VDC

 – plus power for photocell

13

 COM

 – minus power for photocell

13

 COM

 – photocell COM output

14

 FOTO

 – NC contact of the photocell

The power supply of the 24V connector is <450mA, therefore make

sure   that   the   total   power   load   does   not   exceed   this   current   value.  An

exemplary photocells connection diagram is shown in fig. 2.

4.3.

Connection of manual control.

Connection of the manual control should be made with a 2x 0.5mm cable (the cable type

should be in accordance with CEI 20-22; CEI EN50267-2-1 standards), the maximum length of the
manual control cable depends on its electrical parameters, therefore it should be assumed the

following rule that with the required cable length, its resistance should not exceed 100ohm. As a
standard, the use of a cable with a cross-section of 0.5 mm and a length of not more than 20 m is

sufficient for the correct operation of the controller, for required greater distances, 4x0.5 (mm)
cables can be used by connecting the wires in parallel - in pairs, or by increasing the cross-section

of the cable (2x 1mm).

15

 SBS – bell button 

18

 COM 

Next, make the electrical connections of the connector on the left side

as shown in fig. 2.

Summary of Contents for 535Y

Page 1: ...HATO 535Y AUTOMATIC BARRIER OPERATING MANUAL...

Page 2: ...ON electronics 14 DIMENSIONS 14 DRIVER ASSEMBLY 15 CONNECTION DIAGRAM 18 SETTINGS PROGRAMMING 19 1 WARRANTY CONDITIONS 24 Congratulations on your purchase of HATO 535Y automatic barrier and welcome to...

Page 3: ...h the applicable regulations in the field of electrical equipment operation and in accordance with health and safety regulations Do not connect the drive to the power supply earlier than specified in...

Page 4: ...vices helps to protect the environment and ensures that disposal is done in a way that protects human health and the environment This note also applies to waste batteries and accumulators DECLARATION...

Page 5: ...ions 360 230 1050 Max arm length 5m Weight 60kg Number of cycles per hour 200 LIST OF ELEMENTS No Description Quantity 1 Barrier 1 2 Mounting plate for the barrier arm 1 3 Barrier mounting cover 1 4 H...

Page 6: ......

Page 7: ...rs drill CORDS power cord 1 5mm2 signal cord 0 5mm2 FOUNDATION When the foundation is poured under the barrier a PVC pipe should be placed in it min 12mm diameter This way we can secure the cords brou...

Page 8: ...spacing 150mm x 260mm To do this place the barrier on the foundation and mark the holes Then move the barrier and drill the holes Put expansion plugs into the drilled holes or instert the screws into...

Page 9: ...j lub zamkni tej INITIAL ADJUSTMENT Use the handle to manually set the barrier in the opening position Loosen the M4 screw of the opening cam and turn the cam until the green indicator light for limit...

Page 10: ...rwszym otworze 5 6m w sytuacji gdy szlaban jest kr tszy ni 5m nale y zamontowa spr yn w odpowiedni otw r To do this you need to Loosen the spring bringing the barrier to the open position Loosen the n...

Page 11: ...LB11SZ complies with the directives EMC 2014 30 UE LVD 2014 35 UE RED 2014 53 UE ROHS 2011 65 UE MD 2006 42 UE declares that the equipment type HELB11 is in compliance with Directives EMC 2014 30 UE L...

Page 12: ...Manual Keep this installation and operating manual in an accessible place Use the product in accordance with its intended use Observe and comply with the health and safety regulations and standards i...

Page 13: ...an aggressive atmosphere Carry out inspection and maintenance work at least every 6 months INSTALLATION Gates barriers that are automatically opened with a drive must meet the requirements of applicab...

Page 14: ...MODE OF ACTION The drive is controlled by means of a transmitter button programmed in eLB11SZ or a bell button of the SBS sequence control In both cases the operation consists in carrying out the step...

Page 15: ...ke sure that all safety recommendations are met Any installation work may only be performed by qualified personnel Electrical installation and connection of electronic devices may only be performed by...

Page 16: ...er additional protection against crushing in the door clearance They must be connected in series with the photocells Photocells 12 24VDC plus power for photocell 13 COM minus power for photocell 13 CO...

Page 17: ...connecting it Fluorescent lamps must not be used as traffic lights 4 7 Power connection The last stage of connection is to connect the controller power supply connect in turn the wires 2 PE protectiv...

Page 18: ...f the entire automatic unit and all connected safety signaling and control elements limit switches photocells edge strip light signaling etc 11 Set the available additional functions 12 Train all user...

Page 19: ...auto closing time ATTENTION Stopping the gate with a transmitter or control button during closing stops the countdown and to close the gate press the control button again you can use it when you need...

Page 20: ...ress the SETUP button briefly within 3 seconds After 3s from the last press the LED will flash 3 times The controller will remember the settings and return to normal operation WARNING SIGNALS The warn...

Page 21: ...O CL switch to OFF LIMIT SWITCH TYPE The controller works as a standard with electromagnetic switches supplied with 24Vdc voltage and with 24Vdc voltage output signal Depending on whether the voltage...

Page 22: ...nk and the receiver will return to normal operation REMOTE PROGRAMMING OF TRANSMITTERS eLB11SZE Remote programming of transmitters takes place when the barrier is fully open and a 4 channel transmitte...

Page 23: ...NOTES...

Page 24: ...ntor Defects revealed during this time will be removed free of charge The repair will be made as soon as possible not exceeding 14 days from the date of delivery of the device to the HATO POLSKA Servi...

Page 25: ...damage to devices previously dismantled or repaired by unauthorized persons d devices with a damaged illegible incorrectly filled in warranty card or a broken seal e damage to devices used intensively...

Page 26: ......

Page 27: ...HATO TRADE SP ZOO ul eromskiego 1 41 205 Sosnowiec POLAND tel 032 785 25 42 www hato com pl DISTRIBUTOR SELLER...

Reviews: