background image

8. 

Check to see if all gas connections are tight and that all joints have been properly lubricated. 

9. 

Check to see if all condensate drain piping has been completed (if required). 

10. 

Insure that all insulation is fastened securely to walls, ceiling, and floor areas. 

11. 

Check blower supply area to insure freedom of shaft rotation and proper belt tension - Remove any shipping 
blocks and isolation support frame securing bolts (if ordered). 

12. 

Check blower motor to insure that pulleys are secure and drive belts are tight 

13. 

Check filters for cleanliness, and in the case of throw-away filters, make certain that they are free of moisture. 
(Note:  Wet filters will collapse under static pressure and the media will be sucked into the downstream sections 
of the unit.) 

14. 

If any optional dampers are supplied, make certain that all dampers linkage is free to move and that no binding 
will occur.  If dampers are of the modulating type, check control capillary tubes to insure that the tubes will not rub 
against any stationary objects. 

15. 

Check all areas for cleanliness. 

16. 

Secure all access doors. 

17. 

Check all canvas connectors (where used) between the unit and any duct work used. 

18. 

Instructions specify that service personnel shall perform a gas leak check during heater start-up, to verify the gas 
tightness of the heater’s components and piping under normal operating conditions. 

19. 

Adequate instructions shall be provided for adjusting the pilot flame. 

20. 

Adequate instructions shall be provided for checking the gas tightness of the safety shut-off valve(s). 

21. 

Check blower shaft/coupler alignment on units with backward incline fans or split fan sets. 

22. 

Follow all list pre-checks prior to start-up as listed on factory start-up information form sent with equipment. 

G.  START-UP 

All safety and operating controls have been checked during the factory test period, however, it is advisable to complete a 
similar check when first operating the unit. 

1. 

Remove any shipping blocks from (gas units only): 

 

a.  High limit switch (if mercury bulb type) mounted on burner cabinet.  Remove limit switch cover, remove paper 

blocking, and tilt mercury bulb to reset. 

 

b.  Gas pressure switch(es) (if required) may have shipping screws.  Remove screws if supplied. 

 

c.  Unit programming controller may be shipped with a paper shipping block.  Remove programmer cover and 

remove paper shipping block – re-install cover and adjust manual reset. 

2. 

Refer to heater rating plate for determining the minimum gas supply pressure for obtaining the maximum gas ca-
pacity for which this heater is specified. 

3. 

Prior to starting the heating sequence of the system, air needs to be purged from gas supply line up to the Hast-
ings equipment.  CAUTION:  The use of soap bubbles or an electronic leak detector is recommended to check for 
leaks - Do not check for leaks with gas flame torch -  Do not check for leaks with gas flame torch - Do not depend 
on sensing the odor of gas to determine if the air has been purged from the gas line. 

4. 

The unit is equipped with an electronic modulating gas valve which is controlled by a discharge sensor located in 
the discharge opening.  Check to see that the sensor is properly positioned.  Set the selector dial for desired dis-
charge temperature - factory set at 70°. 

5. 

If 70° F discharge temperature is not desired, move appropriate discharge selector dial to new position and set 
inlet air controller to a temperature at least 5° F below this setting. Note:  No adjustment required on modulating 
gas valve.  High and low fire positions are factory set for proper operation.  In some cases, it may be possible or 
desirable to reduce the low fire: be sure to keep continuous flame the full length of burner. 

6. 

Check setting of inlet air controller.  This is factory set at 65° F to shut down burner when outside temperature 
rises above 65° F.  If unit is to be test run when outside temperature is above 65° F, this setting will have to be 
raised for burner to operate. After unit has been test run, reset controller at 65° F. 

7. 

Close gas hand valves and pilot cock. 

8. 

Set all switches to “Off” position. 

- 8 - 

Summary of Contents for DIRECT GAS FIRED ELECTRIC STEAM

Page 1: ...ISSB 1 August 2011 Installation and Service Instructions DIRECT GAS FIRED ELECTRIC STEAM AND HOT WATER NOTICE Read These Instructions before installation ...

Page 2: ...OUR SAFETY If you smell gas 1 Open windows 2 Don t touch electrical switches 3 Extinguish any open flame 4 Immediately call your gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly be fore installing or servicing this equipment FOR YOUR SAFETY The us...

Page 3: ...rouble Shooting the Direct Gas Fired Unit 15 M Trouble Shooting the Electric Unit 17 N Trouble Shooting the Steam or Hot Water Unit 18 SECTION 4 Illustrations Unit Assembly Figure 1 20 Unit Assembly Figure 2 21 Unit Suspension Figure 3 22 Unit Suspension Figure 4 23 Unit Assembly and Suspension Figure 5 24 Unit Assembly and Suspension Figure 6 25 Duct Connections Figure 7 26 Remote Control Panel F...

Page 4: ...re shipped in the same manner as explained above All options and accessories are shipped mounted and wired whenever possible within the limitations of ship ping and handling Any accessories which include wiring that are shipped separate i e intake or discharge dampers require no additional conduit or wiring in the field All wire leads will be tagged for reconnection in the field The SB unit is des...

Page 5: ...ner The burner is a direct fired non premix design with cast iron manifold and stainless steel mixing plates A spark ignited intermittent pilot for natural or propane gas at inlet pressure from 6 ounces through 1 pound is standard The burner is capable of a 22 1 turndown ratio Maximum temperature rise is 119 F 5 Gas and electric Controls The following are furnished as standard components on all di...

Page 6: ...tain there is enough clearance for opening and removing access doors Special attention should be given to supply if required and discharge duct connections Electrical power and control hook up points and steam or hot water supply and return lines if required should also be noted This in formation should be cross checked with the position of support beams and stand pipes to insure that support stru...

Page 7: ...lation All gas piping must comply with Standard of National Board of Fire Underwriters and all applicable local codes Contact factory if exact gas piping dimensions are required Standard pipe caps are furnished on manifold for shipment from factory Run correctly sized gas line to unit Install manual shut off valve and regulator if not already installed Note gas line pressure must be as shown on sp...

Page 8: ...afety lockout red light marked lockout See typical remote control panel illustrated in Figure No 8 in this manual b Optional remote control panel s Same as described above but with the addition of lights and switches de pending upon options ordered 8 Remote Control Panel Specifications Signal Lights Pilot lights are rectangular neon type for 115 V A C service Lights are UL approved and have 18 AWG...

Page 9: ...parate sections All sections are shipped in a horizontal position SB 112 through SB 218 has top mounting channel and base channel shipped assembled with blower burner section SB 222 through SB 240 has top mounting channel shipped as one section but not physically attached to either blower or burner section see Figure No 10 Unit base assembly is shipped separately for field connection to mounting c...

Page 10: ...ing the unit 1 Remove any shipping blocks from gas units only a High limit switch if mercury bulb type mounted on burner cabinet Remove limit switch cover remove paper blocking and tilt mercury bulb to reset b Gas pressure switch es if required may have shipping screws Remove screws if supplied c Unit programming controller may be shipped with a paper shipping block Remove programmer cover and rem...

Page 11: ...s over grooves or sheaves as this results in permanent belt damage 19 Open hand valve and pilot cock 20 Move season switch to winter position to light pilot blower must be operating Amber signal light marked heating should indicate that the burner is operating If pilot does not light depress reset button on programming relay If it becomes necessary to adjust pilot flame check the micro ampere read...

Page 12: ...is causes the valve to call for continuous high fire 2 Remove cap A and turn adjusting screw B to desired low fire adjustment see page 11 3 Replace cap A and reconnect wire to terminal 8 NOTE If calibration of the amplifier or remote temperature selector is necessary place an accurate tem perature measuring device as near the discharge air sensor as possible Set the remote temperature at least 10 ...

Page 13: ...H VALVE ADJUSTMENTS 11 ...

Page 14: ...tch is in the summer position and the three position blower switch is in the on posi tion power is supplied to the blower motor starter Blower relay and blower delay timer must be operational Blower motor will run if blower motor overloads are not tripped Heater is inoperative System white light in remote control panel will be on if auxiliary blower motor starter contacts are closed Optional clogg...

Page 15: ...ar and adjustment See data below 5 Burner Check orifice openings annually contact factory for proper orifice drill size for cleaning Filters check filters at least once each season and clean or replace as necessary Standard filters are of the heavy duty fiberglass mesh throw away type No attempt should be made to clean and re use these filters Replacement filters should be an equivalent to the typ...

Page 16: ...E BELOW DEFLECTION TABLE Belt Cross Section marked on belt Motor Pulley Pitch Diameter Deflection Force Minimum Maximum A 3 0 3 6 2 62 lbs 3 25 lbs 3 8 4 8 3 lbs 4 lbs 5 0 7 0 3 25 lbs 5 lbs B 3 4 4 2 3 lbs 5 lbs 4 4 5 6 4 lbs 5 87 lbs 5 8 8 6 5 25 lbs 7 87 lbs 14 ...

Page 17: ...ial and flashing as required The unit manufacturer will not assume responsibility for leaks if the curb adaptor gasket provided by others and sealing tape provided by others are not used Be careful not to allow gaps where two pieces of sealing tape meet Unit is now ready for setting on the roof SBD 222 227 233 and 240 require a field fabricated sheet metal skirt around base of unit Contact factory...

Page 18: ...properly f Air proving switch is open due to under or over velocity See Item 2b note g Spark gap is approximately 3 8 h Flame rod wire and spark ignition wire for loose connections and or reversed wires i Any electrode insulators are cracked replace as required j Pilot gas valve is open and that pilot has been lit purge pilot gas line to eliminate any air k A three to four micro amp reading for pi...

Page 19: ...er motor must be full open b Low limit temperature control setting too high or n c over riding timer contacts open c Access door switch es open NOTE If other optional controls are supplied on special applications check to see if they are in the electrical circuit 2 If blower runs but remote control panel blower light doesn t come on auxiliary starter contact in magnetic motor starter not closing 3...

Page 20: ...ose and slipping or blower is running backwards Also check to see if air proving sensing tube is plugged or has been crimped 3 If blower operates and blower signal light is on but system fails to heat air to desired temperature check to see if a Season switch in remote control panel is in winter position b Heating relay contacts are closed c Two position or modulating valve and controller if modul...

Page 21: ...4 petcock in a riser off the condensate return ahead of the trap The petcock should be left open for continuous venting Vent air lines should not be re turned to the condensate return main 10 If condensate must be lifted above coil return level into overhead mains or if return mains are pressurized a pump and receiver should be installed between condensate traps and return mains Most of the common...

Page 22: ... 20 ...

Page 23: ... 21 ...

Page 24: ... 22 ...

Page 25: ... 23 ...

Page 26: ... 24 ...

Page 27: ... 25 ...

Page 28: ... 26 ...

Page 29: ... 27 ...

Page 30: ... 28 ...

Page 31: ... 29 ...

Page 32: ... 30 ...

Page 33: ... 31 ...

Page 34: ... 32 ...

Page 35: ... 33 ...

Page 36: ...3606 Yost Avenue Hastings Nebraska 68901 1966 Phone 402 463 9821 Fax 402 462 8006 www hastingshvac com E mail sales hastingshvac com ...

Reviews: