The following recommendations are not intended to supplant requirements of federal,
state or local codes having jurisdiction. All local authorities having jurisdiction should be
consulted before the installation is made. The heater should be installed in accordance
with the standard of the National Board of Fire Underwriters for the class and all wiring
connections must conform to the National Electric Code.
C.
COMBUSTION AIR OPENINGS
When the heaters are installed in a separate heater room with fresh air and return air ducts
running direct to the base of the heater, or when the plant is under a high negative
pressure condition, provisions should be made for an outside source of combustion air. A
conservative rule of thumb for estimating the inlet area required is 90 square inches per
1,000,000 BTU/HR heater output. The following table lists the recommended free area of
vent opening in the outside wall for various heater sizes.
HEATER SIZE
AREA OF COMBUSTION AIR
CONNECTING DUCT
MODEL
INTAKE OPENING – SQ.INCHES
DIAMETER – INCHES
20
18
6
25
22
6
40
36
7
50
45
8
75
68
9
100
90
11
125
113
12
150
135
13
175
158
14
200
180
14
225
202
16
250
225
18
275
248
18
300
270
19
325
292
20
350
315
20
400
360
22
450
405
24
-5-