Furnished and Installed by Others
Furnished By Factory, Installed By Others
Factory Furnished And Installed
ITEM
DESCRIPTION
1
Oil Hand Shut-Off Valve
l
2
Oil Filter
l
3
Oil Safety Valve
l
4
Oil Pressure Gauge
l
5
Burner Oil Pump
l
6
Main Oil Solenoid Valve
l
7
Oil Nozzle
l
8
Oil Cylinder
l
9
By-Pass Oil Solenoid Valve
l
10
By-Pass Pressure Regulator
l
11
Check Valve
l
1
Oil Supply From Oil Supply Pump. Pump Not Furnished By Unit Manufacturer.
2
For Line Pressure Below 60 PSI Only.
3
On Suction Systems, Remove Oil Safety Valve and Pipe As Shown Above.
Burner Pump By-Pass Plug Installed By Unit Manufacturer.
4
Oil Supply Pressure Must Not Exceed 3 PSI Or Pump Seals May Be Damaged.
5
100/125 PSI At Low Fire. 200/300 PSI At High Fire.
6
Two Pipe Systems Only, Oil Return To Supply Tank. Burner Pump By-Pass Plug Installed By Unit
Manufacturer. On One Pipe Systems, Burner Pump By-Pass Plug Removed By Unit Manufacturer.
7
High Fire Position Of Combustion Air Louver.
8
On Gravity Or Pressure Systems, Four Foot Piping Distance Recommended From Center Line Of Oil Safety
Valve To Entering Side Of Burner Oil Pump.
9
Oil Piping Size To Be 3/8” NPT.
Figure 4 – Typical Oil Piping Manifold for Counterflo Heaters