3.
Burner should light and when discharge temperature reaches the limit set point, the
burner should shut down. This should occur within 10 minutes maximum.
4.
Reset Motor Overload Relay and remove jumpers on Air Proving Switch.
5.
Refer to the High Limit Manufacturers’ Installation and Maintenance Manual for further
information.
Cover Plates, Enclosures and Guards
WARNING: All Cover Plates, Enclosures and Guards must be maintained in place at all
times, except during Maintenance and Servicing.
SECTION VI. – TROUBLESHOOTING
A.
TROUBLESHOOTING GAS-FIRED UNITS
1.
If blower fails to operate, check to see if:
a.
Main disconnect switch or circuit breaker is closed.
b.
All main fuses (if disconnect switch used) are in line.
c.
Control transformer is supplying 115 volts to control circuit.
d.
Burner switch in master control panel is “on”.
e.
High limit control is in circuit (manual reset switch).
f.
Magnetic motor starter is in circuit (manual reset starter).
g.
There are any loose wires or connections in blower circuit at either terminal block or
control components.
h.
Bonnet fan switch is in electrical circuit (burner must be operative).
Also check the following optional controls, if used, to see if:
a.
Main gas cock is open – units equipped with manual reset low gas pressure switch
must have gas at switch for proper switch operation..
b.
Low gas pressure switch in circuit (manual reset switch).
c.
High gas pressure switch in circuit (manual reset switch).
2.
If exhauster or combustion air fans fail to operate, check to see if:
a.
Burner switch in master control panel is “on”.
b.
Room thermostat is operational and ambient space temperature is not above
thermostat set point.
c.
High limit switch is in electrical circuit.
d.
Programming relay is functioning properly.
e.
Exhauster/burner starters, or relays if required, are operational and the fuses that
protect them functional.
3.
If pilot fails to light, check to see if:
a. Proper exhaust air/combustion air is being sensed by exhauster/burner air flow
switches.
b. Ignition system is operational.
c. Programming relay is functioning properly.
-26-
Summary of Contents for COUNTERFLO CF SERIES
Page 2: ......
Page 14: ... 11 ...
Page 15: ...Figure 6 Typical Light Oil Piping Suction System Two Pipe Method 12 ...
Page 18: ... 15 ...
Page 22: ... 19 ...
Page 25: ... 22 ...
Page 31: ... 28 ...