6.0 WARRANTY
5.0 MAINTENANCE
5.6 Wye Strainer
The Haskris Chiller is furnished with a
bronze Wye Strainer and 20 mesh
perforated stainless steel screen for
mechanically removing solids from the glycol
solution. Clean the Wye strainer every time
the glycol solution is changed or the return
pressure has increased 10psi or more from
the original value at system start-up. It may
be necessary to remove screen in order to
completely remove all debris.
1) Turn Chiller off.
2) Locate the Wye Strainer.
3) Remove cap.
4) Check screen, remove and clean if
required.
5) Replace screen and cap, ensure cap
is tight and no leaks are present after
unit is started.
Wye
Strainer
Return Pressure
Gauge
Wye Strainer, Screen, Cap