![HARTING 61 12 201 0010 Handbuch Manual Download Page 20](http://html1.mh-extra.com/html/harting/61-12-201-0010/61-12-201-0010_handbuch-manual_601556020.webp)
20
English
HARTING Multiphase Test Connector / 10 B
HARTING Customized Solutions GmbH & Co. KG
Description
Delta circuit
Colour: white
Connected phases (L1, L2, L3)
Colour: orange
DANGER!
Danger of life due to electric shock! The Multiphase Test Connec-
tor is incapable of displaying the absence of power. One phase
may conduct current, even though this is not displayed. For dis-
playing phases L1, L2 or L3, at least two phases must be live!
Rotating field – clockwise
Colour: green
Rotating field – counter-clockwise
Colour: red
5.3 Possible errors
Possible errors
Reasons
Measure / Action
Star symbol is not illuminated
Star bridge is missing
Mount the star bridge
Delta symbol is not illuminated
Delta bridge is missing
Insert the delta bridge
LED for phase L1 (or L2 or L3) is not illuminated Phase is not connected
Check the phase connections
LED for clockwise rotating field is not illuminated At least one phase is not
present
Check the connections for all
phases
LED for counter-clockwise rotating field is not
illuminated
At least one phase is not
present
Check the connections for all
phases
One leg of the star symbol is not illuminated. The
rotating field is not displayed
At least one phase is not
present
Check the phase connection
Two legs of the delta symbol are not illuminated.
The rotating field is not displayed
At least one phase is not
present
Check the phase connection