E018-P
User Manual
FW_E018-P_M_v0301-01_EN
Page 59
HART VARIABLES
QV (quaternary variable)
Not used
The Flowrate value is permanently linked to the PV and the analog output.
Device status information
The E018-P returns its status in the device status byte available through command 48. When the
status flag ‘more status available’ is set, command 48 can return the following status flags in its
additional status bytes:
DEVICE STATUS INFORMATION
B
YTE
D
ESCRIPTION
C
ONTENT
14
E0 error register 1
Fld. Dev.stat 14-1 0x01
Display error
Fld. Dev.stat 14-2 0x02
EEPROM error
Fld. Dev.stat 14-3 0x04
Not used
Fld. Dev.stat 14-4 0x08
Not used
Fld. Dev.stat 14-5 0x10
Low alarm error
Fld. Dev.stat 14-6 0x20
High alarm error
Fld. Dev.stat 14-7 0x40
Linearization error
15
E0 error register 2
Fld. Dev.stat 15-1 0x01
Initialization error
Fld. Dev.stat 15-2 0x02
Warning: Total was cleared (either
via HART or by hand)
FLD. DEV.STAT 14-1 and FLD. DEV.STAT 14-2 are critical errors.
The device malfunction flag is set in device status.
The device malfunction is
not
shown with Namur43-conditions but with a status flag in the device
status through command 48.
Command specific response codes
The following response codes are valid for all implemented commands:
COMMAND SPECIFIC RESPONSE CODES
C
ode
C
lass
D
escription
0
Success
No command-specific errors
1
-
Undefined
2
Error
Invalid selection
3
Error
Passed parameter too big
4
Error
Passed parameter too small
5
Error
Too few data bytes received
6
Error
Device-specific command error
7
Error
In write protect mode
Units
The predefined units in HART are mapped to the E018-P totalizer and flowrate units as follows:
Totalizer
Setup unit
Display icon
DD UNIT
Hart unit number
l
L
L
41
m3
M3
M3/Cum
43
US Gal
gal
gal
40