APPENDIX C - HART COMMUNICATION
This chapter gives a detailed information on the supported HART-commands, variables and status
bits present in the E018-P that are required to connect and operate your HART-enabled device.
HART (Highway Addressable Remote Transducer) is an industrial protocol that must be
superimposed on a 4-20 mA current loop signal. It is an open standard, and full details about HART
can be obtained through the website of the FieldComm Group (previously HART Communication
Foundation) at www.fieldcommgroup.org.
Device Descriptor
All standard HART configuration items are accessible without any special configuration. To configure
all settings of your E018-P device, your host or communicator must use a specific HART Device
Descriptor (DD), especially designed for the E018-P. These DD’s can be downloaded from the
FieldComm Group website (www.fieldcommgroup.org) or the Fluidwell website (www.fluidwell.com).
Identification
Manufacturer Name
Fluidwell B.V.
Model Name
E018-P
Manufacture ID Code
0x6039
Device Type Code
0xE2CD
HART Protocol revision 7.0
Revisions
Device Revision 0x03;
Software Revision 0x01,
Hardware Revision
0x00).
Physical layer
FSK, 4-wire high-
impedance transmitter
Device type / physical
category
DC-isolated Bus Device
Transmitter
Device ID
0x177864
Device profile
0x01
HCF SDC625 tokenized output:
Emerson 475 Field communicator:
Universal commands
All universal commands (including command 38 and 48) are supported.
Common practice
commands
The following common practice commands are supported:
Command 34
Command 35
Command 38
Command 40
Command 42
Command 45
Command 46
Command 48
Command 54
Command 59
Command 100
Set PV damping value
Write PV Range Values
Reset configuration change flag
Enter/Exit Fixed Current Mode
Device Reset
Trim Loop current zero
Trim Loop current gain Read additional device
status
Read additional device status
Read device variable information
Write Response Preambles
Write PV Alarm Code
Number of device-
specific commands
17 (+2 used indirectly)
Number of dynamic
variables
3
Map-able dynamic
variables
No
Additional device
status flags
Yes
Burst mode
No
Alternative operating
modes
No
Catch device variable
No
Write protection
No
Variables
The following E018-P runtime variables are mapped to the HART dynamic device variables:
HART VARIABLES
Type
E018-P
PV (primary variable
Flowrate
SV (secondary variable)
Total
TV (tertiary variable)
Accumulated total