![background image](http://html1.mh-extra.com/html/harsco-industrial/sc-2000/sc-2000_installation-and-owners-manual_4041218017.webp)
Gas Fired Boiler
17
Harsco Industrial, Patterson-Kelley Technical Service 1.877.728.5351
3.5 Inlet Air and Exhaust Venting
3.5.1 Applicable Codes and Standards
Codes
United States:
NFPA 54/ANSI Z223.1 National Fuel Gas Code
NFPA/ANSI 211
Chimneys, Fireplaces, Vents and Solid
Fuel Burning Appliances
Canada:
CAN/CSA B149.1
Installation Codes for Gas Burning
Equipment
Standards
UL 1738
Venting Systems for Gas-Burning
Appliances, Categories II, III and IV
ULC S636-95
Standard for Type BH Venting System
Sheet Metal and Thermoplastic Duct
Construction Manual Air Conditioning
Contractors National Association
(SMACNA)
These codes and standards contain information for the venting of
gas fired appliances, including, but not limited to vent sizing,
location, clearance to combustibles, and safe installation practices.
The installation must comply with both the above Federal Codes
and with state, provincial and local codes.
Table 3.5.1
Required Stainless Steel Vent Adapters and Category II Motorized
Dampers
Boiler Size
Nom.
vent
Size
Stainless
Vent
Adapter
Vent
adapter
size
Boiler
Combustion
Air inlet
Combustion air
N.C. Motorized
Damper
Size
SC-2000 10”
2640000133 10”
12”
1004906946
12”
SC-3000
10”
2640000133 10”
12”
1004906946
12”
SC-4000
10”
2640000133 10”
12”
1004906989
14”
NOTE:
This table is for information only. Combustion air dampers
and vent adapters are listed for use of design and may or may not
be specific to your application.
Design and installation of venting
systems should be done only be
qualified and knowledgeable
venting systems personnel and in
accordance with vent system
manufacturer’s installation
instructions. Installing a boiler or
vent system using improper
installation methods or materials
can result in serious injury or death
due to fire or asphyxiation.
Before connecting a boiler to a
venting system, it must be
determined whether the boiler is to
be installed in a conventional or
direct vent configuration. In the
US, provisions for combustion air
must be in accordance with NFPA
54/ANSI Z223.1, National Fuel
Gas Code, latest edition, or
applicable provisions of the local
building codes. In Canada,
combustion and ventilation air
openings shall comply with
CAN/CSA B-149.1 Natural Gas
and Propane Installation Code.
For correct installation of vent
system, read all of these
instructions and refer to vent
manufacturer’s instructions.
Failure to use a proper vent system
(types and materials), as described
in this manual will void the boiler
warranty and may result in rapid
deterioration of the venting system,
creating a health or life safety
hazard.
Faulty vent installation can allow
toxic fumes to be released into
living areas. This may cause
property damage, injury or death.
Summary of Contents for SC-2000