Hydronics/Water Flow
(SC-1500 / SC-2000)
The chart below represents the pressure drop (Ft of Head) versus the water flow rate (GPM) for the SONIC
TM
SC-1500 and SC-2000 boilers. This information is useful to help size an appropriate circulation pump.
Keep in mind this pressure drop represents the boiler only, additional consideration is needed for any
connecting piping, valves, strainers, couplings, flanges, etc
∆
.
®
SC-1500 / SC-2000
o
∆T
The table below summarizes the minimum and maximum flow restrictions for the SC-1500 and SC-2000
boilers:
Flow Condition
Boiler Operation
Flow Rate
Approximate
∆
T
Maximum Flow
High Fire
192 GPM
20 °F
Minimum Flow
Ignition
48 GPM
20 °F
Minimum Flow
Low Fire
38 GPM
20 °F