MACH
®
Gas Fired Boiler
46
5.6
W
IRING
D
IAGRAMS
5.6.1 Terminal Block Assignments – High Voltage (120 VAC) Circuit (TB2)
Terminal Number
Label
Description
1
120 VAC LINE
Boiler Supply Power, 120 VAC, 1 ph , 60 Hz
2
120 VAC NEUTRAL
Boiler Supply Neutral, 0 VAC
3
120 VAC NEUTRAL
Neutral for use with TB2-10, Switched Output
4
120 VAC NEUTRAL
Neutral for use with TB2-11, 3 Way Valve
5
120 VAC NEUTRAL
Neutral for use with TB2-12, DHW Pump Contactor
6
120 VAC NEUTRAL
Neutral for use with TB2-13, CIRC Pump Contactor
7
120 VAC NEUTRAL
Neutral for use with TB2-14, Damper Output
8
GROUND
Boiler Supply Ground, 0 VAC
9
GROUND
Boiler Supply Ground, 0 VAC
10
120VAC SW OUTPUT
120VAC output when boiler is switched on (pilot duty only)
11
120VAC 3 WAY VALVE
120VAC output during CH Mode. 3 way valve is normally
closed (not powered) for DHW, and powered open for CH
Mode.
12
120VAC DHW PUMP CNTR
120VAC output when boiler is in DHW Mode (pilot duty
only)
13
120VAC CIRC PUMP CNTR
120VAC output when boiler is in CH Mode (pilot duty only)
14
120VAC DAMPER
120VAC output when boiler is enabled (pilot duty only)
15
MASTER ALARM RELAY
This circuit closes when the boiler is in an alarm state
16
MASTER ALARM RELAY
17
FLAME DETECTED RELAY
This circuit closes when the boiler is firing
18
FLAME DETECTED RELAY