Dry Seasoned Wood Only!
TL2.0 Woodburning Stove
Save These Instructions
Harman® • TL2.0 Owner's Manual_R20 • 2011 -___ • 09/15
C
A
G
F
D
B
E
24" (610 mm)
Minimum vertical
prior to elbow.
Vertical Vent, Horizontal Exit
Location
Single-Wall Pipe
A
Unit to Side Wall
13" / 330mm
B
Unit to Back Wall
13" / 330mm
C
Vent Pipe to Side Wall
23" / 584mm
D
Vent Pipe to Back Wall
18" / 457mm
E
Vent Pipe to Ceiling
16" / 406mm
Corner Installation
F
Corner to Adjacent Wall
16" / 406mm
G
Connector to Wall
22-1/2" / 571mm
For clearance reduction methods, refer to NFPA 211 or Local Codes
Follow NFPA 211 Table 13.6.1 "Clearances for Solid Fuel–Burning Appliances" for clearance from the top of the
unit to ceiling.
This unit was not tested for installation into an Alcove. Follow NFPA 211 Table 13.6.1 "Clearances for Solid Fuel–
Burning Appliances".