background image

4

PC 45 Corn/Pellet Stove

3-90-02686R29_05/14

Installation

Installing

Place the stove on a noncombustible floor or floor protector that extends a 

minimum of 6" (152mm) to the front of the load door opening, 6" (152mm) 

to the sides of the door opening, and 6" to the rear. Floor protection must 

also extend 2" (51mm) beyond each side of any horizontal flue pipe. The 

minimum floor protector material is 20 gauge sheet metal. Other floor 

protector materials are ceramic tile, stone, brick, etc.

NOTE for Canadian installation only:

 Per ULC-S627-00, If installed 

on  a  combustible  floor,  the  need  to  provide  a  noncombustible 

floor 

protector 

covering the area beneath the 

space heater 

and extending 

at least 17.72" (450mm) on the firing side and at least 7.87" (200mm) 

on the other sides.

In  Canada,  you  may  follow  smaller  U.S.  floor  protection 

requirements ONlY if the user agrees to completely shut-down 

the appliance, and allow it to cool to where all fire is extinguished 

and the combustion blower and its indicator light shuts off, prior 

to opening the firebox door or ash door.

Place the stove away from combustible walls at least as far as shown in 

Figures 3 and 4. Please note the difference in side wall clearance with 

and without side shields. 
Note that the clearances shown are minimum for safety but do not leave 

much room for access when cleaning or servicing. Please take this into 

account when placing the stove. 
Connect the power cord to a 120 VAC, 60 Hz grounded receptacle. (A 

surge protector is recommended to protect the circuit board.) Also be 

sure that the polarity of the outlet that the stove is plugged into is correct.
Prior to installing the flue pipe, connect a draft meter. (The draft meter 

must have a minimum range of 0 - .5") Record the first reading. Connect 

flue pipe to stove and be sure all doors and windows in the home are 

closed. Record the second draft reading_______. If the second reading is 

more than .05" lower than the first reading, check for possible restrictions 

or  the  need  for  outside  air.  For  more  information  on  the  draft  test 

procedure, refer to the draft adjustment procedure located in this manual.

mobile home Installation

When installing this unit in a mobile home, several requirements must 

be followed: 

1.  The unit must be bolted to the floor. This can be done with 1/4" lag 

screws through the 2 holes located in the base plate.

2.  The unit must also be connected to outside air.

3.  Floor protection and clearances must be followed as shown.

4.  Unit must be grounded to the metal frame of the mobile home.

CAuTION: This appliance must be vented to the outside.

Due to high temperatures, the stove should away from traffic, furniture 

and draperies.
Children and adults should be alerted to the hazards of high surface 

temperatures and should stay away to avoid burns to skin and/or clothing.
Young  children  should  be  carefully  supervised  when  they  are  in  the 

same room as the stove.
Clothing  and  other  flammable  materials  should  not  be  placed  on  or 

near this unit.

Minimum  size  rectangular  floor  protection  (USA)  is 

28

5/16

" Deep By 24

3/4

" Wide.

*Floor  protection  dimensions  for  the  front  and  sides  are 

measured  from  the  appliance  door  opening  in  The  United 

States. In Canada, the side dimension is measured from the 

widest part of the appliance.

l

j

Floor Protection 

requirements

US

Canada

Sides

Rear

6" 

200mm

6" 

200mm

K

Front

6" 

450mm

Fig. 3

9"(228mm)With Side Shields

13"(330mm) Without Side Shields

Fig. 4

2"(51mm)

36"(914mm)

14" (355mm) with 
side shields

18" (457mm) 
without side shields

14" (355mm)

18" (457mm)

9"(228mm)-

13"(330mm) 

9"(228mm)-

13"(330mm) 

Alternate floor protector 

dimension may be used 

as long as they satisfy the 

measurement requirements 

shown below.

Minimum size floor protection 

for a corner installation 3 

pad is 36" x 36". Clearance 

shown as 9" with optional side 

shields installed.

j

uSA

K

l

j

CANAdA

NOTE:

 

Measurement "L" is 

measured from the 

pedestal base in 

the US ONLY

NOTE:

 

Measurement "K" 

is measured from 

the glass in the US 

ONLY

F

loor

 

protector

ThE STruCTurAl INTEgrITY OF ThE 

mANuFACTurEd hOmE FlOOr, wAll, ANd CEIlINg/

rOOF muST bE mAINTAINEd.

dO NOT INSTAll IN SlEEPINg rOOm.

WARNING

!

Summary of Contents for PC45

Page 1: ...onnaire de Harman Save these instructions Installation Operating Manual Model s PC45 Freestanding Corn Pellet Stove NOTICE SAVE THESE INSTRUCTIONS Hot glass will cause burns Do not touch glass until i...

Page 2: ...is uniquement Measured from Glass Opening Mesurer partir de la surface de la porte en verre Floor Protection Must Be a Non Combustible Material MustAlso be Place UnderAny Horizontal Flue Connector Ext...

Page 3: ...e burnpot Fig 2 Follow these instructions along with all local codes regarding installation of this appliance Do NOT use makeshift compromises when installing this appliance serious consequences may r...

Page 4: ...heck for possible restrictions or the need for outside air For more information on the draft test procedure refer to the draft adjustment procedure located in this manual Mobile Home Installation When...

Page 5: ...r assembly when measured from the horizontal center line of the regulator V Vent Terminal A Air Supply Inlet Area where termination is not permitted Door Sidewalk Fixed Closed Openable Openable Fixed...

Page 6: ...corn burning The sections of pipe lock together to form an air tight seal however in some cases a perfect seal is not achieved For this reason and the fact that the PC45 operates with a positive vent...

Page 7: ...wever consideration must be given to the total house demand House demand may consume the air needed for the stove It may be necessary to add additional ventilation to the space in which the appliance...

Page 8: ...od This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and...

Page 9: ...excellent venting for normal operation This method also provides natural draft in the event of a power failure The damper area must be sealed with a steel plate Kaowool mineral wool or an equivalent n...

Page 10: ...Be sure to use approved pellet vent pipe fittings Seal pipe joints with silicone in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Insta...

Page 11: ...bustible materials are allowed within 3 of the PL vent pipe flashing storm collar 1 MIN 1 MIN 1 2 M I N 1 MIN Fig 15 12 min wall to outlet 36 min clearance to any combustible material Fig 17 DO NOT IN...

Page 12: ...with a burn pot that has 125 1 8 combustion air holes This grate has no identifying marks Included with your stove is an additional grate that has 0625 1 16 combustion air holes This grate can be iden...

Page 13: ...uit board switches The pellet kit contains the instructions for the conversion a new burn pot end gate and a new combustion blower inlet ring The combustion blower inlet ring on the left is the one or...

Page 14: ...e setting can be adjusted within the full range between 1 on the low side to 6 on the high side Overfeeding is not a safety concern but the fire may be pushed off the burnpot and extinguish in the ash...

Page 15: ...you to check the motors for operation NOTE The auger motor will not operate with the view door or ash door open NOTE The initial start up on a new stove may require the corn to be purged into the burn...

Page 16: ...EMP AUTO MANUAL IGNITER FEED ADJUSTER PELLET ONLY C O R N PELLET Manual Stove Temperature Mode Igniter Switch to MANUAL Room Temp Mode The fire will have to be lit with starting gel and a match or sta...

Page 17: ...ll reset the control and start the combustion motor 3 Turn the Temperature Dial to the desired setting 4 Clean the burnpot and housing if necessary 5 Fill the burnpot with pellets so that the auger tu...

Page 18: ...when pointer is not within off position band except after normal shut down Blinks to indicate errors listed below Indicates power to Distribution Blower 6 Blinks Indicates that the control has calcula...

Page 19: ...itch will not allow the feeder motor or the igniter to operate A simple draft test should be performed after completing the flue pipe installation To record the results for future reference Combustion...

Page 20: ...container with a tight fitting lid The closed container of ashes should be placed on a noncombustible floor or on the ground well away from all combustible materials pending final disposal If ashes ar...

Page 21: ...ombustion blower wheel and flue outlet Fig 33 7 Clean the blower wheel with a brush and a vacuum cleaner Soot and Fly Ash Formation and Need For Removal The products of combustion will contain small p...

Page 22: ...basic ways 1 Because the corn slag buildup will absorb moisture from the air when cool the parts can just be left exposed for several days and the slag buildup will crumble off of the parts 2 To acce...

Page 23: ...Lay the glass into the door making sure that the glass is contained within the channels and raised areas of the door itself Lay the glass retainers into position and install the screws Tighten each s...

Page 24: ...too rich a Feed rate too high b Draft too low caused by a gasket leak 2 Unit is in an ignition cycle Troubleshooting LOW HEAT OUTPUT 1 Feed rate too low 2 Temperature setting too low Stove Temp Mode...

Page 25: ...fuel with high moisture content takes energy to dry and tends to cool the appliance thus robbing heat from your home Damp pellet fuel could turn back into sawdust which does not flow properly through...

Page 26: ...02686R29_05 14 Specifications 23 1 2 10 35 1 2 5 1 4 12 3 8 29 1 2 Weight 249 lbs Blower 135 CFM Feed Rate 0 to 5 0 lbs per hr Hopper Capacity 80 lbs Fuel Corn Wood Pellets Flue Size 3 Inch Outside Ai...

Page 27: ...installs behind the trim on the ash door Cleaning Plated Trim Gold or nickel plated hardware should never be buffed or polished Abrasive cleansers and metal polishes will remove the plating and theref...

Page 28: ...e room sensor is essential for the PC45 s excellent efficiency NOTE It is recommended that the room sensor be installed even if only installed on the rear of the unit as a return air sensor Fig 43 Fig...

Page 29: ...OUND 18 3 RUBBER CORD N O WHITE BLUE GREEN WHITE GREEN RED ESP PROBE 6 AMP GLASS FUSE PART NO 3 89 02676 BLUE FEEDER AUGER MOTOR PUMP BLACK RED REMOTE SENSOR PORTS IGNITOR ELEMENT MALE FEMALE CONNECTI...

Page 30: ...e construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs...

Page 31: ...is warranty does not cover the following Changes in surface finishes as a result of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is...

Page 32: ...shut down Your appliance will pulse the blower every few seconds to clear exhaust until the fire is out NOTE The UPS provides safe shut down only It is not intended for continued operation Your applia...

Page 33: ...33 PC 45 Corn Pellet Stove 3 90 02686R29_05 14 Service Maintenance Log Date Of Service Description Of Service Performed By...

Page 34: ...34 pC 45 Corn pellet Stove 3 90 02686R29_05 14 Service Maintenance Log Date Of Service Description Of Service Performed By...

Page 35: ......

Page 36: ...e This powerful heating appliance boasts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels Signature of Boxer Your premium quality hearth prod...

Reviews: