Instruction Manual | 9
SAFETY INSTRUCTIONS
•
For UL compliance, the CE family of ICSLan Device Control Boxes should be powered directly via any listed external IEC/UL
60950-1 2nd edition certified LPS PoE switch or injector, such as the AMX NXA-ENET8POE or PS-POE-AF.
•
The CE-series family of ICSLan Device Control Boxes are intended for Network Environment 0 per IEC TR62101, and are to
be connected only to PoE networks without routing to the outside plant.
Preparing/Connecting Captive Wires
1.
Strip 0.25 inch of wire insulation off all wires.
2.
Insert each wire into the appropriate opening on the connector according to the wiring diagrams and connector types
described in this section.
Note: Do not tighten the screws excessively; doing so may strip the threads and damage the connector.
LAN/PoE Port
The LAN/PoE (RJ45) port on all CE Modules provides 10/100 BaseT network connectivity. Use standard Cat5/6/6E ethernet cable to
connect the CE Module to the LAN. The Ethernet Port LEDs show communication activity, connection status, speeds, and mode
information:
•
SPD (speed) - Yellow LED lights On when the connection speed is 100 Mbps and turns Off when the speed is 10 Mbps.
•
L/A (link/activity) - Green LED lights On when the Ethernet cables are connected and terminated correctly, and blinks when
receiving Ethernet data packets.