Installing the Accentra52i-TC Pellet Insert into a Harman Zero Clearance Cabinet
If you don’t have a factory built fireplace or masonry fireplace, the Accentra52i-TC Pellet Insert can also be installed into
the Harman Zero Clearance Cabinet, Part # 1-00-574323. This is the
only permissible
way to install the Accentra52i-TC
Pellet Insert without a suitable fireplace. After the Harman Zero Clearance Cabinet is installed, type PL vent pipe, wall
pass-throughs and terminations are used (
Note:
Flex pipe is not approved these types of installation). Detailed installation
instructions are included with the Zero Clearance Cabinet. These same installation instructions can also be found on-line at
www.harmanstoves.com.
Below are two sample installations using the Harman Zero Clearance Cabinet.
PL Vent Pipe installed through a ceiling.
PL Vent Pipe installed through an exterior wall
Harman Zero Clearance Cabinet
Requirements for Terminating the Venting through an
Exterior Wall.
The clearance to a window or door that may be opened must
be a minimum of 48" to the side and 48" below the window/
door, and 12" above the window/door. (
with outside air
installed, 12” to the side or below
)