Accentra 52i Pellet Insert Zero Clearance Cabinet
Part #1-00-574323
10
3" MIN.
3" MIN.
3" MIN.
3" MIN.
Flashing
Storm Collar
12" MIN.
No insullation or other
combustible materials
are allowed within 3” of
the PL Vent Pipe.
Unless specified by the
pipe manufacturer
PL Vent manufacturer’s firestop
space and support
Venting clearances for in room installation of the Zero Clearance Cabinet.
NOTE:
• Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY.
• Illustrations/diagrams are not drawn to scale.
• Actual installation may vary due to individual design.
NOTE:
In Canada, where passage through a wall or partition of combustible construction
is desired, the installation shall conform to CAN/CSA-B365.