Harman 300i Wood Insert
9
For Installation In Masonry Fireplace Only
3-90-300101
Harman® • 300i Wood Insert Owner’s Manual_R13 • 2010 -___ • 04/15
Steel Plate
Tile Liner
Sealing Plate
Chimney Cap
For direct connect and positive connect installations, ensure
that the liner is securely connected to the insert flue collar.
Clearances
Clearance is the empty space required between the insert
and the nearest combustible surface or object, such as
walls, ceilings, floors, or furniture. Clearance distances may
only be reduced by methods listed in the standard CAN/
CSA B365 (Canada) or NFPA 211 (USA). Contact your
local building authority prior to attempting any clearance
reduction.
From the front of the insert, the clearance to combustible
materials such as furniture, curtains or fuel is; 48" (1215mm)
in the U.S. and 60" (1525mm) in Canada.
The clearance from the top of the insert to a 12" (305mm)
mantel is 30" (762mm), and to facing trim, 1-1/2" (38mm)
thick, is 20" (508mm).
The clearance from the side of the insert to facing trim,
1-1/2" (38mm) thick, is 13-5/8" (345mm) and from the insert
to a side wall is 29-5/8" (752mm).
Mantel
30" (762mm)
20" (508mm)
29-5/8" (752mm)
13-5/8" (345mm)
Facing trim (1-1/2"/38mm
maximum)
WARNING
!
DO NOT INSTALL IN SLEEpINg ROOM.
CAUTION
!
MAkESHIFT COMpROMISES MADE DURINg
InstallatIon or alterIng any sUpplIed part
or coMponent May present a safety hazard
AND ARE ExCLUDED FROM THE pRODUCT
warranty coverages.
WARNING
!
do not connect thIs UnIt to a chIMney flUe
SERvINg ANOTHER AppLIANCE.