16
Pellets or Corn/Pellet Mixture Only 3-90-775 Save These Instructions
P35i Fireplace Insert
F. Optional Zero Clearance
Cabinet Installation:
If installing using the optional zero clearance cabinet,
Item
#1-00-774257,
the venting will need to exit through
the top of the cabinet. The vent can be vertical or
horizontal after leaving the cabinet. Once clear of the
cabinet, a 90 degree elbow can be installed for rear
termination as shown. Do not allow vent pipe seams to
fall within the cabinet wall. Use proper wall thimble as
supplied by the venting manufacturer.
If finishing the interior with stone or masonry, the venting
can be installed without the appliance. Install the cabinet
and secure the venting using the Flue Rough-in Support
#1-00-774283.
The top of the chimney must also be sealed.
Otherwise, it can become a nesting area or a
water trap.
If passing through combustible
material, the proper thimble from the
vent manufacturer must be used.
M
asonr
y w
all
3" Clearance
Zero Clearance Cabinet
shown with Flue Rough-in
Support
Vent pipe seams must be
accessible.
Ver
tic
al
Ven
ting ma
y b
e used in a c
onstr
uc
ted chase
pr
oviding all clear
anc
es t
o c
ombustibles ar
e met.
Proper wall pass-thru device
as recommended by the
venting manufacturer.
E. Existing Fireplace, Rear Vent:
Notice the side edges of the surround contain slotted
openings. These openings allow room air to be drawn into
the rear of the cabinet and circulated through the heat
exchange and back into the room. These openings can not
be blocked. If finishing with stone or
masonry keep the masonry a minimum
of one inch from the sides of the
surround. Mortar can be used to give a
more finished look.
NOTE:
When installed in a rear vent
configuration, the maximum BTU
may be reduced due to elevated ESP
temperatures associated with the
horizontal exhaust stream.