Function description

█ Phase control

Phase control is to control the AC power supply applied to the load proportionally 

according to the control input signal as changing phase angle (0 ~ 180 degree) in a each 

half cycle, 8.33 ms.

50%

ON

50 % Output control

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

20%

ON

OFF

20 % Output control

ON

OFF

80%

80 % ON

20 % OFF

80 % Output control

40 %

40 % ON

80 % OFF

40 % Output control

25 % Control

Output

Contact

signal

50 % Control

75 % Control

100 % Control

1. Please install it vertically like a picture above,  If the product is installed vertically in 

     unavoidable circumstances, please use 50 % of rated current.

2.  When multiple products are closely installed, please install them with keeping a 

distance of more than a width of 5 cm and a length of 10 cm as as shown in the 

    picture below.

3.  In order to not block the air flow, please install the wiring duct less than the half of the 

heat sink height.

4.  Please consider whether the air flow is good enough when installing the product. 

     If the ambient temperature is as low as possible in the inside then the life span of the     

product is increasing as the durability and reliability of the product are improving. 

     The operating  ambient temperature is 0 ℃ ~ 40 ℃. 

5. When wiring, please use crimp connectors to high current flows terminal. If the contact 

     surface of the connectors and terminals are poor, it may lead to a fire since the wires     

and terminal gets overheated

6.  Before applying power, this model need more than the third class grounding to 

prevent electric shock. 

     This model does not have separate grounding terminal so we suggest using grounding     

terminal and bracket together when install this model to a panel.

Installation

█ Fixed cycle control

As setting the constant cycle of the output, (1 sec), fixed cycle control is to control the AC 

power supply repeatedly with a constant rate of ON/OFF according to the control input.

50%

ON

50 % Output control

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

20%

ON

OFF

20 % Output control

ON

OFF

80%

80 % ON

20 % OFF

80 % Output control

40 %

40 % ON

80 % OFF

40 % Output control

25 % Control

Output

Contact

signal

50 % Control

75 % Control

100 % Control

█ Variable cycle control

Without setting a constant cycle, variable cycle control is to control AC power supply 

with using the number of cycle.

50%

ON

50 % Output control

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

20%

ON

OFF

20 % Output control

ON

OFF

80%

80 % ON

20 % OFF

80 % Output control

40 %

40 % ON

80 % OFF

40 % Output control

25 % Control

Output

Contact

signal

50 % Control

75 % Control

100 % Control

Appearance

[Unit : mm]

Connection diagram

█ Connection diagram of load terminal

· There is no fuse inside the power regulator (TPR).

   It is recommended to use an external fuse separately.

· Please use a crimp terminal to tighten the terminal when tightening the 

   terminal due to a high current flows. 

   (Tightening terminal space of crimp terminal: 15 mm)

143.5

157.5

150

145

50

94

110

4-6.5

28, Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea

TEL : +82-32-876-4697     FAX : +82-32-876-4696 

http://www.hanyoungnux.com