31
B
ef
or
e staring
Installation
Op
er
ation
Sp
ecifications
Register address (HEX)
Parameter
Description
Property
(R/W)
Setting range
Unit Initial value
CH1
CH2
CH3
CH4
n : Number of
channel
154(9A) 254(FE) 354(162) 454(1C6)
AP
Set 2 DOF PID ALPHA
R/W
1 ~ 100
ABS
50
155(9B) 255(FF) 355(163) 455(1C7)
MR
Set Manual Reset
R/W
0.0 ~ 100.0
%
0.0
156(9C) 256(100) 356(164) 456(1C8)
CT
Set control cycle
R/W
1 ~ 100
Sec.
RELAY
: 30 Sec.
S.S.R :
2초 Sec.
157(9D) 257(101) 357(165) 457(1C9)
PO
Set emergency output
R/W
0.0 ~ 100.0
%
0
158(9E) 258(102) 358(166) 458(1CA)
HYS
Set hysteresis at ON/OFF
control
R/W
EUS (0 ~ 10%)
℃
EUS
(0.2%)
159(9F) 259(103) 359(167) 459(1CB)
RO
Set output at stop,
monitor status
R/W
0.0 ~ 100.0
%
0
160(A0) 260(104) 360(168) 460(1CC)
RUP
Set SV increase
temperature at RAMP
control
R/W
EUS (0 ~ 100%)
℃
EUS (0%)
161(A1) 261(105) 361(169) 461(1CD)
RDN
Set SV decrease
temperature at RAMP
control
R/W
EUS (0 ~ 100%)
℃
EUS (0%)
162(A2) 262(106) 362(16A) 462(1CE)
RMIN
Set SV change time (min.)
at RAMP control
R/W
0 ~ 1000
Minute
0
163(A3) 263(107) 363(16B) 463(1CF)
RHRS
Set SV change time (hr.)
at RAMP control
R/W
0 ~ 100
Hour
0
164(A4) 264(108) 364(172) 464(1D0)
DR
Set control run
R/W
0: Reverse run
(heating) control
1: Forward run (cooling)
control
ABS
0
(Reverse
run (heating)
control)
165(A5) 265(109) 365(173) 465(1D1)
OHL
Set high limit to
Manipulated Value
R/W
0.0 ~ 100.0
%
100.0
166(A6) 266(10A) 366(174) 466(1D2)
OLL
Set low limit to
Manipulated Value
R/W
0.0 ~ 100.0
%
0.0
171(AB) 271(10F) 371(173) 471(1D7)
BS
Set input correction
R/W
EUS (-100 ~ 100%)
℃
EUS (0%)
172(AC) 272(110) 372(174) 472(1D8)
FL
Set input filter
R/W
0 ~ 100
ABS
0
173(AD) 273(111) 373(175) 473(1D9)
SVH
Set SV high limit
R/W
EU (0 ~ 100%)
℃
EU (100%)
174(AE) 274(112) 374(176) 474(1DA)
SVL
Set SV low limit
R/W
EU (0 ~ 100%)
℃
EU (0%)
175(AF) 275(113) 375(177) 475(1DB)
FRH
Set PV high limit
R/W
EU (0 ~ 100%)
℃
EU (100%)
176(B0) 276(114) 376(178) 476(1DC)
FRL
Set PV low limit
R/W
EU (0 ~ 100%)
℃
EU (0%)
177(B1) 277(115) 377(179) 477(1DD)
SLH
Set scale high limit at
DCV input setting
R/W
EU (0 ~ 100%)
mV
EU (100%)
178(B2) 278(116) 378(17A) 478(1DE)
SLL
Set scale low limit at
DCV input setting
R/W
EU (0 ~ 100%)
mV
EU (0%)
179(B3) 279(117) 379(17B) 479(1DF)
DOT
Set decimal point
R/W
0 ~ 3 :
decimal point digit
ABS
0
Summary of Contents for ML-D2H