Multi Loop Controller
20
Register range
Details
4
0 0 0 1 ( 0 ) ~
4
0 0 9 9 ( 6 3 )
CH1~2 PV, SV, MV, TSV, CHSTS, EVSTS and common channel setting ※ Please use address
4
0000 for Modbus
communication
4
0 1 0 1 ( 6 5 ) ~
4
0 1 9 9 ( C 7 )
CH1 related setting
4
0201(C9) ~
4
0299(12B)
CH2 related setting
Register address
(HEX)
Symbol
Description
Property
(R/W)
Setting range
Unit
Initial
value
CH1
CH2
n : Number
of channel
1(1)
2(2)
PV
Process value
R
EU(0 ~ 100%)
℃
-
6(6)
7(7)
SV
Set value
R/W EU (0 ~ 100%)
℃
EU (0%)
11(B)
12(C)
MV
Manipulated Value
R
0.0 ~ 100.0
%
-
16(10)
17(11)
CHSTS
Channel status
R
OR run for situation occurrence
15 Bit: Set “1” at System Data error
14 Bit: Set “1” at Calibration Data error
13 Bit: Set “1” at input circuit error
12 Bit: Set “1” at EEPROM error
11 Bit: Set “1” after 24 hours of auto toning (AT)
10 Bit: Set “1” at standard contact point correction
(RCJ) error
9 Bit: Set “1” when exceeding ±5% input range
8 Bit: Set “1” at input sensor error (B. OUT)
2 Bit: Set “1” at auto tuning (AT) running
1 Bit: Set “1” at monitor mode
0 Bit: Set “1” at run start
ABS
-
21(15)
22(16)
TSV
Target set value
R
EU (0 ~ 100%)
℃
EU (0%)
26(1A)
EVT_STS
Event status
R
Indication of occurrence to all events previously set
0: no event occurred
1: event occurred
ABS
-
27(1B)
EVBUS_STS
Event Bus output
status
R
Event bus output OR run
7 Bit(128): Set “1” at event bus8 output occurrence
6 Bit(64): Set “1” at event bus 7 output occurrence
5 Bit(32): Set “1” at event bus 6 output occurrence
4 Bit(16): Set “1” at event bus 5 output occurrence
3 Bit(8): Set “1” at event bus 4 output occurrence
2 Bit(4): Set “1” at event bus 3 output occurrence
1 Bit(2): Set “1” at event bus 2 output occurrence
0 Bit(1): Set “1” at event bus 1 output occurrence
ABS
-
31(1F)
LOCK
Parameter change
lock
R/W
0: possible to edit all parameters
1: possible to edit only SV, R/S, AT, CHEN
parameters
2. impossible to edit all parameters
ABS
0
32(20)
COMCHK
Time setting for
RS485 communication
disconnection detection
time
R/W 0 : OFF
1 ~ 3,600
sec. 0 (OFF)
33(21)
PARA_SAVE Setting of communication
used parameter save
R/W
0: Automatic parameter save
1: save manually using PARA_COPY
parameter
ABS
0
34(22)
PARA_COPY
Run parameter save R/W 1: When PARA_SAVE “1” is set, save
parameters manually
ABS
0
36(24)
37(25)
CHMD.n
Set channel mode
R/W
0:Stop mode
1: Monitor mode
2: Run mode
ABS
0
41(29)
42(2A)
AT.n
Run PID auto tuning (AT) R/W 0: PID auto tuning (AT) stop
1: PID auto tuning (AT) start
ABS
0
46(2E)
R/S
Run setting
R/W 0: run stop (STOP)
1: run start (RUN)
ABS
0
3.2.2 ML-D2H register description