2
A100h
JANUARY 2020
DO NOT SUBSTITUTE OR MODIFY
Because of the danger of introducing additional hazards,
do not install substitute parts or perform unauthorized
modifications to the equipment.
CLEANING/DECONTAMINATION
EXTERNAL SURFACE
The external surface, excluding the sensor element, can
be cleaned using light detergent and water. Do not allow
any of the solution to come in contact with the sensing
element sintered surface.
Remote Gas Detector
2 or 8 Channel Gas Detector Controller
Handheld Gas Detector
AMBIENT TEMPERATURE RANGE
-40°F (-40°C) to 120°F (50°C)
-4°F (-20°C) to 122°F (50°C)
-13°F (-25°C) to 131°F (55°C)
VOLTAGE REQUIREMENTS
24 VDC + 18%, 24 VAC + 20%
100-240 VAC, 50/60 Hz, 80W max
'D' Cell BaVery
HUMIDITY RANGE (NON-CONDENSING)
5-90% RH, 15-90% RH (electrochemical)
5-90% RH
0-95% non-condensing
OUTPUTS
4-20mA, 0-5V, 1-5V, 0-10V, 2-10 VDC
RS485 Modbus RTU Slave
RS-232, 0-1 VDC analog
4-20mA SIGNAL OUTPUT
Isolated 2-wire
N/A
N/A
ALARMS
(3) SPDT RELAY, 1A @ 30V resisave load
(3) SPDT RELAY, 1A @ 30V resisave load
High, low, off
ALTITUDE
0-2,000m
N/A
N/A
ENCLOSURE
IP67
NEMA 1
N/A
ACCURACY
SC - <-10%/+15%, IF/EC - < + 5%
N/A
5%
Start-up / Warm-up Time
SC - 15min*, EC - 5min*, IF - 2 min*
N/A
Up to 24hrs if not biased
Approvals
CE/EN 50270:2015/UL/CSA/IEC/EN 61010-1
UL/CSA/IEC/EN 61010-1 CE
N/A
* Up to 400% longer at temperature limits
TABLE 1