– To prevent the formation of a flammable
gas-air mixture in the event of a leakage
in the refrigeration circuit, the installation
space must have a minimum size of 1 m
3
per 8 g of refrigerant in compliance with
the EN 378 standard. The amount of re-
frigerant contained in your appliance can
be found on the data sheet at the end of
this user manual.
The minimum size of the area in which your
appliance is set up is as follows: 6.5 m³
– The appliance must only be placed on a
level and firm surface. The surface must be
strong enough to support the appliance’s
weight when fully laden.
– Suitable locations are dry, well-ventilated
areas that are cool if possible.
– Unsuitable locations are ones with direct
sunlight or which are directly next to an
oven, hob or radiator.
– The following minimum distances must be
maintained:
– from electrical hobs
10 cm
– from oil and coal burning stoves 30 cm
– from other cooling appliances
10 cm
– from washing machines/
dishwashers
10
cm
– If you would like to reduce these distances,
you can fit an insulation plate between the
appliances.
– If underfloor heating is installed at the set-
up location, place the cooling appliance on
an insulation plate made from solid mate-
rial.
Space required when setting up as a free-standing appliance
A:
1880 mm
B:
600 mm *)
C: 50 mm
D: 668 mm *)
E:
1178 mm *)
F:
30 mm
G: 50 mm
H: 135°
I:
1015 mm *)
*) Including handle
Start-up
Page EN-22