HI520 Dual-Channel Universal Process Controller
Quick Reference Guide
Please retain for future use.
QR520 12/22
Controller wiring
•
Terminal 1
(high voltage):
POWER
,
ALARM
,
REL 1
to
REL 5
(relays)
•
Terminal 2
(low voltage):
COMM
(RS-485),
PROBE1
and
PROBE2
,
IN1
and
IN2
(digital inputs),
A01
to
A04
(analog
outputs)
• Follow lead markings to ensure output leads are wired
to the correct position on the main board.
COMM
- B A +
IN1 IN2 A01 A02 A03 A04
PROBE
- B A +
Terminal 1
Terminal 2
PROBE 1
- B A +
PROBE 2
- B A +
INP
- I +
A +
B
—
A +
B
—
Probe wiring
1. With controller disconnected from power run the probe cable
through the correct conduit opening.
2. Connect probe leads to the terminal connector
PROBE1
or
PROBE2
.
Follow lead markings for correct wiring of output leads.
3. Carefully put the wired terminal connector into place on the board.
4. Position excess cable through cable gland before tightening the nut.
5. Remove the ground screw and hardware located below the probe
connector. Attach the ground lead (
g
).
Probe cabling color code
Marking Attached Cable
Patch Cable
Functionality
–
GREEN
BLACK
0 V
B
WHITE
WHITE
RS-485 D –
A
YELLOW
BLUE
RS-485 D+
+
BROWN
RED
5 V
g
GREEN-YELLOW
GREEN-YELLOW
PROTECTIVE GROUND
Terminal 1
Terminal 2
Supported probe series and configurations
HI10
X X
–
Y
8
Z Z
pH & Temperature
XX
06
PTFE
junction
16
Ceramic
junction
Y
Glass sensor
Titanium Matching Pin
pH range
Temperature range
1
Low
temperature
0.00 to 12.00 pH
–5.0 to 80.0 °C
(23.0 to 176.0 °F)
3
High
temperature
0.00 to 14.00 pH
0.0 to 100.0 °C
(32.0 to 212.0 °F)
4
Fluoride
resistant
0.00 to 10.00 pH
–5.0 to 60.0 °C
(23.0 to 140.0 °F)
HI20
X X – Y
8
Z Z
ORP & Temperature
XX
04
PTFE
junction
14
Ceramic
junction
Y
Sensor type
mV range
Temperature range
1
Platinum
± 2000 mV
–5.0 to 100.0 °C
(23.0 to 212.0 °F)
2
Gold
HI7630
– Y
8
Z Z
EC & Temperature
Y
2
Two-electrode
cell conductivity,
SS AISI 316,
cell constant
k ≈ 0.1/cm
EC 0.000 µS/cm to 30.00 mS/cm
TDS 0.000 mg/L to 15.00 g/L (TDS factor 0.5)
RES 34 Ω•cm to 99.99 MΩ•cm
Temperature 0.0 to 50.0 °C (32.0 to 122.0 °F)
4
Four-ring
conductivity,
platinum on glass,
cell constant
k ≈ 1.0/cm
EC 0.0 µS/cm to 999.9 mS/cm
TDS 0.0 mg/L to 400.0 g/L (TDS factor 0.5)
RES 1.00 Ω•cm to 9.99 MΩ•cm
Seawater Salinity 400.0 %NaCl, 42 psu, 80 ppt
Temperature 0.0 to 100.0 °C (32.0 to 212.0 °F)
HI7640
–
1 8
Z Z
Galvanic DO & Temperature
Galvanic
sensor
Concentration 0.00 to 50.00 mg/L (ppm)
Saturation 0.0 to 500.0 %
Temperature −5.0 to 50.0 °C (23.0 to 122.0 °F)
HI7640
–
5 8
Z Z
Optical DO & Temperature
Optical
sensor
Concentration 0.00 to 50.00 mg/L (ppm)
Saturation 0.0 to 500.0 %
Temperature −5.0 to 50.0 °C (23.0 to 122.0 °F)
8
Smart probe
, with RS-485 connection
ZZ
00
supplied with DIN connector (without cable)
05
,
10
,
15
,
25
,
50
fixed cable length (in meters)
pH
ORP
EC
Galvanic DO
Optical DO
Probes are sold separately.