HESS-OF-S-10K
Empowering Energy Clean And Affordable
38
No
Protection Feature
Instruction
11
Inverter over-load protection
After triggering the overload protection the inverter will resume output
after 3 minutes, 5 consecutive overloads will switch off the output until
the inverter is restarted.
(102%<load<110%) :
alarm
and output shutdown after 5min;
(110% < load < 125%):
alarm
and output shutdown after 10s.
Load > 125% :
alarm
reported and output switched off after 5s.
12
AC output reverse
Prevents AC back flow from the battery inverter to the bypass AC input.
13
Bypass over-current protection
Built-in AC input over-current protection circuit breaker.
14
Bypass phase inconsistency
protection
When the phase of the bypass input and the phase of the inverter split do
not match, the inverter disables switching to the bypass output to prevent
the load from dropping out or short-circuiting when switching to the
bypass.