HESS-OF-S-10K
Empowering Energy Clean And Affordable
20
ID
Parameter Meaning
Options
Description
00
Exit
ESC
Exit the setup menu.
01
AC output source priority
UTI default
Utility at first priority, utility and solar provide power
to load at the same time when solar is available,
battery will provide power to load only when utility
power is not available.
SbU
Solar power and battery at first priority,Utility will
provide power to load when solar power is not
available and the battery voltage below parameter
[04] value.
SOL
Solar power at first priority, Utility will provide power
to load when solar power is not available and the
battery voltage below parameter [04] value .
02
AC output frequency
50.0 default
AC output frequency will adaptive utility frequency
in bypass mode.Otherwise the output will follow the
preset value.
60.0
03
AC input voltage range
UPS default
When output range is 220/230V, input voltage
range 170~280V
APL
When output range is 220/230V, input voltage
range 90~280V
04
Voltage point of battery
switch to utility
43.6 default
When parameter1= SBU=SOL, output source will
switch to utility from battery when the battery
voltage below the preset value. Setting
range:40~60V
05
Voltage point of utility switch
to battery
57.6 default
When parameter 1=SBU/SOL, output source will
switch to battery from utility when the battery
voltage above the preset value. Range:40~60V
06
Battery charging mode
SNU default
Solar and utility charging the battery at the same
time, solar at the first priority, utility power as a
supplement when solar power is not
sufficient.Notice: Solar and utility charging the
battery at the same time only in bypass mode, only
solar charging can be used when the invert circuit is
in operation
CUb
Utility is the first priority in charging, Solar charging
the battery only when utility is not available.
CSO
Solar is the first priority in charging, Utility charging
the battery only when solar is not available
OSO
Only solar charging the battery.
07
Battery charging current
60 default
HESS-OF-S-10K current setting range:0~200A.