HESS-OF-S-10K
Empowering Energy Clean And Affordable
29
5.6、Battery parameter
•
Lead-acid battery
Battery type
Parameter
Sealed
Lead Acid
(SLD)
Gel lead
acid (GEL)
Flood lead acid
(FLD)
User-defined
(User)
adjustable
Overvoltage disconnect voltage
60V
60V
60V
60V
Recharge recovery voltage after charging (37
items)
52V
52V
52V
52V
√
Equalize charging voltage
58.4V
-
59.2V
40~60V
√
Boost charging voltage
-
-
-
40~60V
√
Float voltage
55.2V
55.2V
55.2V
40~60V
√
Undervoltage Alarm Voltage (01 Fault)
44V
44V
44V
40~60V
√
Undervoltage alarm restores voltage(01
failure)
Undervoltage alarm v0.8V
Undervoltage disconnect voltage (04 fault)
42V
42V
42V
40~60V
√
Undervoltage disconnect recovery voltage(04
fault) (35 setting items)
52V
52V
52V
52V
√
Discharge limit voltage
-
-
-
40~60V
√
Over-discharge delay time
5s
5s
5s
1~30s
√
Equalization duration
120 min
-
120 min
0~600 min
(adjustable)
√
Equalize charging interval
30 days
-
30 days
0~250 days
√
Boost charging duration
-
-
-
10~600 min
√
○
!
NOTICE
Voltage
Equalization charging voltage
Bulk charging voltage
Float charging voltage
Battery full recharge point
Float
Equalization
termly
time
Current
Equalization
termly
Stage1
Constant current
Stage3
Float
Maintenance
time
Bulk
Absorption
Absorption
Bulk
Float
Stage2
Constant voltage