42
A
B
B Set:Pt100
Ω
/Pt1000
Ω
(Optional)
A Set:PTC
U
V
W
Figure 18 INT69HBY & PTC connection diagram
Other major functions are described follow:
1. When supply voltage is applied, the output relay pulls in after an initialization period of 3 seconds (approximately),
provided all thermistors lie below their rated response temperature.
2. 1 to 9 PTC thermistors with varied rated response temperatures can be connected in series to input terminals.
3. If any thermistor resistance increases above trip level the relay drops out. This failure results in a lockout. (5 minutes
delay for the 1st PTC failure, 60 minutes delay for the 2nd failure, eternal lockout for the 3rd failure until manual
reset)
4. Lockout and time delay can be cancelled by mains reset of approx. 5 seconds.
5. LED with red/green light provides operational information.
6. The relay is fed out as a N/O dry contact, which is closed under good conditions.
7. Sensor and supply circuits are galvanic isolated.
Note: Motor protector phase monitor (phase loss and phase sequence) function is not suitable for variable frequency
drive application.
Technical data of INT69HBY
●
Supply voltage
AC 50/60 Hz 115/120V-15…+10% 3VA
AC 50/60 Hz 230/240V-15…+10% 3VA
●
Ambient temperature
-30…+70
℃
●
Relay output
max. AC 240V, max. 2.5A, C300
min.
>
24V AC/DC, >20 mA
Figure 19 INT69HBY Blink codes display
e. Oil heater
One UL approved 150W oil heater has been installed in every compressor as a standard accessory. Before restart of
compressor after shutdown for a long time, please turn on oil heater at least 8 hours to make the temperature inside
compressor higher than system temperature and ambient temperature. This action prevents condensed refrigerant
inside oil sump of compressors which may result in liquid compression in following operations and poor lubrication due
to low viscosity of lubrication oil. Hanbell also offers 300W oil heater to keep adequate lubricant oil temperature for
large external oil separator and applications in areas where the ambient temperature is low.
Error Blink Codes
PTC Temperature Error
1st: 5min time delay after PTC < R reset
3rd: Lockout after three consecutive PTC
2nd: 60min time delay after PTC < R reset
Timer delay active (PTC < R reset)
Short
interruption
Internal error
temp errors within 24hrs
Long
interruption
Auto reset for INT69HBY
,but not for M-PI-S28
Summary of Contents for RC2-1020AV
Page 15: ...4 3 RC2 AV series compressor outline drawings ...
Page 16: ...15 ...
Page 17: ...16 UNIT SI mm Imperial in ...
Page 18: ...17 ...
Page 19: ...18 ...
Page 20: ...19 ...
Page 21: ...20 ...
Page 22: ...21 ...
Page 23: ...22 ...
Page 24: ...23 ...
Page 25: ...24 ...
Page 26: ...25 ...
Page 27: ...26 ...
Page 28: ...27 ...
Page 29: ...28 ...
Page 30: ...29 ...
Page 31: ...30 ...
Page 32: ...31 ...
Page 33: ...32 ...
Page 34: ...33 SI mm Imperial in UNIT ...
Page 35: ...34 ...
Page 36: ...35 ...
Page 37: ...36 ...