LT-S-(L) Technical manual
INT276LN
Technical Parameters
:
No.
Project
Parameter
No.
Project
Parameter
1
Power supply voltage
AC50/60Hz
230V±10%
4
Power
supply
delay
3s±1s
2
Ambient temperature
range
-30
℃
...+60
℃
5
Action delay
5s±2s
3
Mirror
maximum
temperature tolerance
+120
℃
6
Relay level
AC 240V 2.5A
Size and installation
INT276LN
Note
:
1.
Ensure Photoelectric connector thread and lens cleaning
;
2.
Thread the module along the end of the mechanical part to ensure that the
electrical terminals are vertically downward
;
3.
Fasten external connection nut with bare hands
Compressor delay control instructions
When setting the photoelectric liquid level switch time, in order to avoid the
compressor frequency failure stop when the oil level fluctuation occurs, this product
can set the delay of 60-90 S and then cut off the compressor power supply.
Therefore,
it is recommended to set the time delay for the photoelectric level switch control to be
60-90 seconds.
That is, when the compressor is running, if the oil level detected by the optical