HANBAY Inc
User Manual RDx-B-xxxDT-10.31 Battery Fail Safe
Page 4 of 8
www.hanbayinc.com
Rev. 1 2019
1 800 315 4461
DiP 3
Reserved for custom functions
DiP 4
DiP 5
DiP 6
DiP 7
DiP 8
With DIP switch 8 in the ON position, the actuator will move to 4 positions. When switch 8 is off, the
actuator is limited to three positions. Switch 8 also changes the function of the output signals.
DiP 9
Run / Calibrate
Putting DIP switch 9 into the off position will disable the actuator positioning control, and the motor
will not move regardless of the input signals.
When DIP 9 is moved back into the on position, the actuator will perform it's homing routine, and then
move to the position commanded by the input signals.
DiP 10 DiP 11
Description
Approximate stall current
Off
Off
Low torque
0.75A
Off
On
Medium-low
1A
On
Off
Medium-high
2A
On
On
High torque
3A
Approximate stall torque
DiP 10
DiP 11
RDL
RDM
RDH
RDF
RDU
Off
Off
40 in-lbs
120 in-lbs
405 in-lbs
756 in-lbs
3348 in-lbs
Off
On
53 in-lbs
160 in-lbs
540 in-lbs
1008 in-lbs
4464 in-lbs
On
Off
60 in-lbs
180 in-lbs
608 in-lbs
1134 in-lbs
5022 in-lbs
On
On
65 in-lbs
195 in-lbs
657 in-lbs
1241 in-lbs
5440 in-lbs
DiP 12
DiP 12 sets the direction of rotation
Functionality of the RDx-B-xxxDT:
The RDx can operate as a 3-position or 4-position actuator. The 4
th
position is enabled by turning Dip 8 ON.
3-pos Functionality (Dip 8 OFF)
Input#1
(Pin 1)
Input#2
(Pin 2)
Action taken
High
High
Moves to or remains in center position
Low
High
Moves to or remains in right position
High
Low
Moves to or remains in left position
Low
Low
Moves to or remains in right position (Input#1 has precedence
over Input #2)
The feedback from the RDx-B-xxxDT is as follows:
Output#1
(Pin 3)
Output#2
(Pin 4)
Meaning
High = 4.5vDC Low = 0.8vDC
High
High
Actuator output is in center position
High
Low
In Right position
Low
High
In Left position
Low
Low
Actuator is moving, or has stalled and given up trying to reach
a requested position.
You may retry to reach any position again by setting Input#1
and Input#2. I.E.: toggle Input #1 low for a few milliseconds
and back to high if this was what you were asking for initially.
If the problem persists, you have to trouble shoot the unit.
Top View
onto valve or
other
appliance
Center
Right
Left