Appendix 

 

Calibration 
 

The center position calibration routine can be initiated by switching DiP

9 momentarily “on” then “off”. This will cause 

the actuator to go through a series of movements to determine the proper center position. This function is useful if 
the actuators output gear gets manually rotated while the actuator is powered down and can’t properly realign to the 
center by itself. 

 
 

Troubleshooting: 
 

Upon noticing a problem, your first step should almost always be to recalibrate the actuator by switching DiP 9 on 
then off, all while the actuator is powered. This alone can solve basic problems. See section 3 on this page for more 
details. 
 

If the actuator does not move, try following these steps:  

1) 

Re-calibrate the actuator. This will move the actuator regardless of what signal it is receiving.  

2) 

A sticking valve may be the problem. Remove the valve from the actuator, and re-test the actuator.   

3) 

Remove power. Re-check the wiring and the power/signal apparatus. Power actuator, and re-calibrate. If  
the problem persists, please call Hanbay for technical support.

 

 
 
Battery Fail Safe Function: 
 

In the event of a loss of power or signal, the battery will maintain power to the P1 processor and trigger the actuator 
to move the valve to it’s designated fail-safe position, using power from the battery. 
The TTL outputs will indicate the position of the valve, as in normal operation. 
Once the valve has reached it’s fail-safe position, and after 25 seconds, the P1 processor will go into sleep mode to 
preserve the battery life. 
The actuator will not respond to commands until the power supply is restored. 
The battery will maintain a charge for up to 2 months without power being applied. 
The fail-safe actuation can be performed for 30 cycles on the charge available in the battery. 
During normal operation, from totally discharged, the batteries will take 2 hours to re-charge. 
If in a critical fail-safe application, the fail-safe function should be tested monthly. 
 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for RD-B Series

Page 1: ...ation pg 1 3 Mounting pg 1 Wiring pg 2 Connecting power and signal pg 2 3 Operation pg 3 5 DIP Switch settings pg 3 Functionality pg 4 5 Appendix pg 6 7 Calibration pg 6 Troubleshooting pg 6 Battery f...

Page 2: ...nected to 24vDC to allow the batteries to charge The power consumption will range from max 3 0A to approx min 100mA when the actuator is active When not moving the actuator draws less than 30mA if the...

Page 3: ...ght valves Longer settling times will allow heavier valves to reach their target positions trying to use a fast settling setting on a high torque valve will increase current consumption when holding p...

Page 4: ...008 in lbs 4464 in lbs On Off 60 in lbs 180 in lbs 608 in lbs 1134 in lbs 5022 in lbs On On 65 in lbs 195 in lbs 657 in lbs 1241 in lbs 5440 in lbs DiP 12 DiP 12 sets the direction of rotation Functio...

Page 5: ...tuator is operated using input 1 an automatic calibration is done every time the valve is actuated This does not happen on input 2 Torque Settings Effect of power settings and speed settings To accomm...

Page 6: ...icking valve may be the problem Remove the valve from the actuator and re test the actuator 3 Remove power Re check the wiring and the power signal apparatus Power actuator and re calibrate If the pro...

Page 7: ...HANBAY Inc User Manual RDx B xxxDT 10 31 Battery Fail Safe Page 7 of 8 www hanbayinc com Rev 1 2019 1 800 315 4461 hanbaysales hanbayinc com Main Dimensions...

Page 8: ...HANBAY Inc User Manual RDx B xxxDT 10 31 Battery Fail Safe Page 8 of 8 www hanbayinc com Rev 1 2019 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Reviews: