HAMWORTHY HEATING LTD
16
WESSEX MODU
MAX
100 SERIES
500001123/C
4. The flame ionisation signal generated whilst the boiler is firing, can be viewed directly from the display screen.
The value is set to read dc µA. Refer to
section 8.2.1 - Controls Operation.
5. To ensure correct ignition of the boiler it is recommended to check the resistance of the hot surface igniter. This
should be checked cold, using a suitable ohmmeter, by disconnecting the igniter from the control panel cable and
measuring the resistance across the pins of the 2 way connector. The reading should be between 70 and 110
ohms.
Flame Signal Assessment
Figure 7.2.4 - Ignition Check