AHP60 26/32 kW -
Installation, Use and Maintenance
Figure 16 - Beta 3435 sensor ohmic value
T [°C]
R [Ohm]
T [°C]
R [Ohm]
-40.0
191908
60.0
3012
-30.0
112877
70.0
2221
-20.0
68471
80.0
1663
-10.0
42739
90.0
1262
0.0
27396
100.0
970
10.0
17999
110.0
755
20.0
12099
120.0
594
25.0
10000
130.0
473
30.0
8308
140.0
380
40.0
5819
150.0
308
50.0
4151
Error code
Error designation
Probable causes
Solution
E961
Abnormal condition (reduce
frequency for stop)
Driver output current or housing
temperature exceeded the
protection limits. The rotor may
be stopped since a long time.
Reduce compressor load
Reduce ambiant air
temperature or increase the air
flow
Unplug the compressor cabling
and launch the driver without
compressor.
E971
EEPROM not initiated
The memory card may be
damaged
Restart the driver, replace the
mothercard if the failure is
continuous
REMARK
: The current levels of overcurrent in the software are :
23,5 Arms. 380V : 40 A peak. Instantaneous
6.4.
Ohminic values of the different probes