18 / 74
00U07362400-A_EN
AHP60 26/32 kW -
Installation, Use and Maintenance
2.4.2. Electrical data for the unit and auxiliaries
* Acceptable vari /- 10%.
REMARK: The electrical data may be modified. You must consequently refer to the data label on the RH side
panel of the appliance.
2.4.3. Sound emissions
The acoustic pressure datas are calculated from the acoustic power level in compliance with
norm ISO 3744:2010 regarding heat pumps field operation.
2.4.3.1.
Full load
The noise levels are for the units under full load in normal test conditions in heating mode
in compliance with the provisions of the regulation UE 813/2013 (dry temperature (humid
temperature) of the external air = 7°C (6°C), in/out water temperature = 47-55°C). The tolerance
on the value of the total acoustic power level is 2 dB (A). The value is determined in compliance
with EN 12102-1: 2017, used together with EN ISO 9614-2 which describes the test methods
with the intensimetric method.
Unit power supply
V/~/Hz 3N~400V-50Hz*
TYNEHAM Heat Pump Control com-
mand circuit
V/~/Hz
12/01/1950
Integrated command
circuit
V/~/Hz
12/01/1950
Power supper to fans
V/~/Hz
3N~400V-50Hz
Models
in kW
Acoustic power level per octave band dB(A)
Acoustic
power level
[LW(A)]
dB(A)
Acoustic
power
level at 1m
dB(A)
Acoustic
power level
at 10m
dB(A)
63 Hz 125 Hz 250Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
26
47.5
57.2
64.8
62.1
66.0
61.4
55.1
70
54.1
38.5
32
48.8
58.0
65.6
62.9
68.1
63.7
57.4
72
56.1
40.5