2
80-150 kW Frame & Header Kits Manual
This kit is suitable for the following boilers:
Stratton mk3 80,100,120 & 150 using Natural Gas and 80,100 & 120 using Propane
IMPORTANT
THESE KITS CAN BE USED IN CONJUNCTION WITH
LOW LOSS HEADERS & PLATE HEAT EXCHANGERS
SUPPLIED AS PART OF THE STRATTON MK3 OPTIONS RANGE
CONTENTS
1 Introduction .....................................................................3
2 General Description of Systems ...................................3
3 Multiple Boiler System Components ............................6
4 Frame Kit Installation Procedure ..................................9
5 Header Kit Assembly ....................................................10
6 Installation Drawings for Multiple Boiler Systems ....13
7 Electrical Connections & Wiring Diagram ..................20
8 Commissioning and Testing ........................................22
Boiler
Water Header Size
Maximum No. Boilers
in Cascade
Maximum Output
in Cascade (kW)
S3-80
DN80
4
320
S3-100
DN80
4
400
S3-120
DN80
3
360
S3-150
DN100
3
450
Stratton mk3 - DISCLAIMER
Not all cascades included in this manual are available at initial product launch.
For availability refer to the table below:
Note:
This information will be updated in the next revision of this manual
.