Figure No. 11 - Gas Flow in Pipes
The above table expresses pipe lengths from gas meter to appliance which will produce approx. 1mbar pressure
loss. This table must be used in conjunction with losses of various fittings fitted in the gas line shown below.
For example: - 2 Purewell 120kW Boilers being fed by 2
1
/
2
” pipe with 6 elbows between gas meter and boiler
header can have a maximum length of 72m - (6 x 2m) = 60 metres run to achieve a 1mbar loss.
Note! Information above is based on IM/16.