HAMWORTHY HEATING LTD
92
Merley Boiler Sequence Controller
500001210/D
Climatic conditions
Storage to EN 60721
-
3
-
1
class 1K3, temp.
-
20…65
°C
Transport to EN 60721
-
3
-
2
class 2K3, temp.
-
25…70
°C
Operation to EN 60721
-
3
-
3
class 3K5, temp. 0...50°C (non
-
condensing)
Weight
Without packaging
54 g
8.5 Wireless outside sensor AVS13.399
Power supply
Batteries
2 pcs
Type of batteries
1.5 V alkaline, size AAA (LR03)
Battery life
approx. 2 years
Interfaces
RF transmitter
BSB
-
RF
frequency band 868 MHz
Degree of protection and
safety class
Degree of protection of housing to
EN 60 529
IP20
Safety class to EN 60 730
low
-
voltage
-
carrying parts meet the require-
ments of safety class III, if correctly in-
stalled
Degree of pollution to EN 60 730
Normal pollution
Standards, safety, EMC,
etc.
CE conformity to
EMC directive
-
Immunity
-
Emissions
Low
-
voltage directive
–
Electrical safety
Radio
89/336/EEC
-
EN 61000
-
6
-
2
-
EN 61000
-
6
-
3
73/23/EEC
-
EN 60730
-
1, EN 50090
-
2
-
2
EN 300 220
-
1 (25
-
1000MHz)